 (5)  
The overfrequency and underfrequency circuits are set to operate at 425 to 435 Hz and 360 to 370 Hz respectively. A time delay of 0.25 to 0.60 second prevents transients from the generator causing the GB to trip. The circuit also provides for a lockout of undervoltage protection during normal shutdown of the system.


 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 24-21-00
 ALL  ú ú 03 Page 8 ú Mar 15/95
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
115V ACGEN 1 OA
OB
OC L7
L8
S3 OA
OB
OC
TO N238
ANN LTS
MDL MAN
TRIP LT TO APU

DIFFERENTIALPROTECTION
EPCCLOSE
APU
GB
CLOSE

C889 APU GEN DIFFNC BKR 1 PROT
TEST
POINT C891 EXTERNALPOWER CONTACTOR 1MANUAL TRIP OR EP TRIP
APU GB TRIP TRIP
TO G7
D58 PIN 15

OV - OVER VOLTAGEUV - UNDER VOLTAGEOF - OVER FREQUENCYUF - UNDER FREQUENCYDP - DIFFERENTIAL PROTECTIONOC - OVER CURRENT TR
CONTROLPOWER
28V DC C4SUPPLY
CONTROL
GENERATOR 1
(P6-4)

TRIP
P6  LOAD CONTROL - RIGHT
CLOSE OFFP5-5 D1086K602 GCR PIN 50 (CSD)LOCKOUT K603GCR TO M400 OCDP
OV NORM TRIPUV TO G3 FIRE SEE
FIG. 6
S8  ENG 1 FIRESWITCH (P8)
ON
S3  GEN 1 SWRESETK601 TO VOLTAGESEEREGULATOR
TO K2TO G724-41-00(P6)FIG. 2
TO S4
TO K801

(G5) K801PR
K1  GEN 1
RELAY

P5-4  AC SYSTEM GEN ANDAPU PANEL K3/K4 28V DCLOGIC
K604 GB TRIPCONTROL
G5  APU GENCONT UNIT G3 GENERATOR CONTROL UNIT 1 (P6)
Generator Control Simplified SchematicFigure 3 (Sheet 1)
BUS TRANS OA
TRANSFER
TRANSFER
BUS OFF

FU
BUS OFF
BUS

F T
O
BUS
OFF

OFF
GEN OFF

GEN OFF
BUS

APU GENBUS
OFF BUS
OFF OFF
ON ON
GEN 1 APU GENGEN 2
APU

P5-4  AC SYSTEM GENERATORAND APU PANEL
TRIP
115V ACGEN BUS 1
R349 XFRCONT RLY 1 MASTER
CAUTION A
MASTER TESTAPRESS TO TEST
L7  BUS 1 OFF LIGHTMASTER DIM
B
B
TOL8 GEN 1 OFF BUS LIGHT
R349TRANSFERP5-4 AC SYSTEM GENERATOR ANDCONTROLAPU PANELRELAY
NOTE:  GENERATOR 1 SCHEMATIC SHOWN.GENERATOR 2 APU GENERATORSCHEMATICS SIMILAR.
CLOSE
C801  GENERATOR BREAKER 1
(RIGHT SIDE-NOSE
WHEEL WELL)

A 737-300/400/500MAINTENANCE MANUAL
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. AIRPLANES WITHOUT SB 24-1115 ú

 24-21-00
 ú ú 05 Page 9 ú Nov 12/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
H54796
115V ACGEN 1
OA
OB
OC
TO N238ANN LTSMDL MANTRIP LT
NCMANUAL TRIP OR EP TRIP
APU GB TRIP
TO G7
D58 PIN 15
OV - OVER VOLTAGEUV - UNDER VOLTAGEOF - OVER FREQUENCYUF - UNDER FREQUENCYDP - DIFFERENTIAL PROTECTIONOC - OVER CURRENT TR
CONTROL
28V DC

POWER
C4SUPPLY
CONTROL
GENERATOR 1
(P6-4)

TRIPP6 LOAD CONTROL - RIGHT
P5-5 D1086
CLOSE OFFK602 GCR PIN 50 (CSD)LOCKOUT K603 GCR TO M400OCDP
OV NORM TRIPUV TO G3 FIRE SEE
FIG. 6 S8 ENG 1 FIRESWITCH (P8)
ON
S3 GEN 1 SW RESETK601 TO VOLTAGESEE REGULATOR
TO K2TO G7
24-41-00(P6)
FIG. 2
TO S4
TO K801

(G5) K801PR
K1 GEN 1
RELAY

P5-4 AC SYSTEM GEN ANDAPU PANEL K3/K4 28V DCLOGIC
K604 GB TRIPCONTROL
G5 APU GEN
CONT UNIT G3 GENERATOR CONTROL UNIT 1 (P6)

Generator Control Simplified SchematicFigure 3 (Sheet 2)
L7
L8

S3 .A
.B
.C TO APUDIFFERENTIALPROTECTION
EPCCLOSE
APU
GB
CLOSE

DIFFPROT
TESTPOINT
TRIP
BUS TRANS OA
TRANSFER
TRANSFER
BUS OFF

FU
BUS OFF
BUS

F T
O
BUS
OFF

OFF
GEN OFF

GEN OFF
BUS

APU GENBUS
OFF BUS
OFF OFF
ON ON
GEN 1 APU GENGEN 2
APU

P5-4 AC SYSTEM GENERATORAND APU PANEL
TRIP
115V ACGEN BUS 1
R349 XFRCONT RLY 1
MASTERCAUTION A
MASTER TESTAPRESS TO TEST
L7 BUS 1 OFF LIGHTMASTER DIM
 