(b)
Thermometer - 0 to 160°F range with accuracy to |2°F
(2) C21001-16 Equipment Cooling System Performance Test Set (alternative)
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. APLS WITH EFIS ú
21-58-02
ú ú 01 Page 506 ú Nov 12/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A 737-300/400/500MAINTENANCE MANUAL
INBD
USE STATIC PROBE TO MEASURE PRESSURE
EFIS Equipment Cooling System Test Ports Figure 501
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. APLS WITH EFIS ú
21-58-02
ú ú 02 Page 507 ú Nov 15/95
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
737-300/400/500
MAINTENANCE MANUAL
PROBE
____ ARROWS SHOW AIRFLOW DIRECTION.
NOTE:
ALWAYS INSERT PROBE INTO DUCT OR
PLENUM WITH THE PROBE TIP FACING
UPSTREAM. VARY PROBE POSITION
SLIGHTLY IN ALL DIRECTIONS TO GET
THE MAXIMUM PRESSURE READINGS
(SMALLEST NEGATIVE PRESSURE).
PROBE POSITIONING
NOTE: 1. DO NOT USE PRESSURE PROBE
2.
1/8" PLASTIC TUBE 2-3 INCHES INTO END OF SUCTION
TUBE. DO NOT INSERT TUBE MORE THAN 3 INCHES.
3.
MAKE SURE THAT PLASTIC TUBE IS HELD IN SUCH
A MANNER THAT FINGERS OR HANDS CANNOT
RESTRICT FLOW AT END OF SUCTION TUBE.
PRESSURE GAGE
Static Pressure Probe and Measurement Methods Figure 502
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. APLS WITH EFIS ú
21-58-02
ú ú 01 Page 508 ú Jul 15/98
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
Pressure Correction BAROMETRIC PRESSURE (IN. HG)
A737-300/400/500MAINTENANCE MANUAL
Gage Pressure Correction Chart
Figure 503
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù.APLS WITH EFIS ú
21-58-02
úú 01 Page 509 ú Nov 15/95
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
1.
Obtain local ambient barometric pressure (Pbar).
2.
Measure E/E bay air temperature (Tbay).
3.
Locate E/E bay temperature on left axis of table and follow row to the column corresponding to the Barometric pressure.
Read the correction factor (Cf).
4. Calculate the corrected pressure (Pcor)
as follows:
Pcor = P*Cf (Where: P is measured E/E
pressure) Bay
_______Example Temp
O2P = 2.6 IN. H (`F)
Pbar = 3.01 IN. HG
Tbay = 46`F
From table: (45`F/30.2 IN. HG) Cf = 0.95
2O2O*0.95 = 2.47 IN. HPcor = 2.6 IN. H
NOTE____
For ambient conditions outside the range of
the table, the correction factor must be
calculated as follows:
10 28.7 29.0 29.3 29.6 29.9 30.2 30.5 30.8
0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86
15 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87
20 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88
25 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89
中国航空网 www.aero.cn
航空翻译 www.aviation.cn
本文链接地址:737-300 400 500 AMM 飞机维护手册 空调 AIR CONDITIONING 2(89)