21-58-00
ALL ú ú 04 Page 508 ú Feb 18/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
E. Put the Airplane to its Usual Condition
S 865-172
(1)
Do the procedure to put the Air/Ground Relay System back to the ground mode (AMM 32-09-02/201).
S 865-088
(2)
Remove the electrical power, if it is not necessary
(Ref 24-22-00/201).
TASK 21-58-00-705-062
5. Operational Test - Low Flow Detector Test
_________________________________________
A. References
(1) 24-22-00/201, Manual Control
B. Access
(1) Location Zone 121 Forward Cargo Compartment Forward Half, LH
C. Prepare for the Test
S 865-063
(1)
Supply electrical power (Ref 24-22-00/201).
S 865-064
(2)
Make sure the EQUIP COOLING selector, on the P5 panel, is in the NORM position.
D. Do the Test
S 715-009
(1) Do a test of the low flow (cooling effect) detectors.
CAUTION: DO NOT LET BOTH FANS STAY OFF FOR MORE THAN FIVE MINUTES.
_______ EXTENDED OPERATION OF AIRPLANE SYSTEMS WITHOUT COOLING AIRFLOW CAN RESULT IN DAMAGE TO EQUIPMENT.
(a) Open the circuit breaker 414R30 EQPT COOLING SUPPLY FAN on P414 power distribution center-left.
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
21-58-00
ALL ú ú 04 Page 509 ú Feb 18/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
(b)
Open the circuit breaker 415R14 EQPT COOLING EXH FAN on P415 power distribution center-right.
(c)
Make sure that in approximately 70 seconds these messages are shown:
~.................................................. | EICAS Caution | EQUIP COOLING | .................................................... | EICAS Status | EQUIP LOW FLOW | .................................................... | EICAS Status | FLT DK LOW FLOW | .................................................... | EICAS Status | EE CLNG SUP FAN | .................................................... | EICAS Status | EE CLNG EXH FAN | 2.......................…..........................1
(d)
Close the circuit breaker 414R30 EQPT COOLING SUPPLY FAN on P414 power distribution center-left.
(e)
Close the circuit breaker 415R14 EQPT COOLING EXH FAN on P415 power distribution center-right.
(f)
Set the EQUIP COOLING switch on the P5 overhead panel to OVRD, then back to NORM.
(g)
Make sure there are no equipment cooling messages shown on EICAS.
(h)
Make sure the ground crew call horn is off.
E. Put the Airplane to its Usual Condition
S 865-012
(1) Remove the electrical power, if it is not necessary (Ref 24-22-00/201).
TASK 21-58-00-705-120