(2)  
Ground Test - E/E Detector
 (3)  
Operational Test - Override Mode Test
 (4)  
Operational Test - Bypass Valve and Supply/Exhaust Fan Test
 (5)  
Operational Test - Low Flow Detector Test
 (6)  
Operational Test - E6/E9 Valve
 (7)  
System Test - Differental Pressure Switch Test
 (8)  
System Test - E30 Rack Pressure
 (9)  
System Test - E1/E2 Rack Pressure
 (10)
 System Test - CARGO FIRE Switch Test
 (11)
 System Test - Electrical Test
 B.  The electrical system test does a check of the equipment cooling system in each mode of operation. The test also includes a check of the overheat switch.
 C.  The Equipment Cooling ground test includes a check of the clean cycle logic.
 D.  The Detector Ground Test does a check of the equipment cooling low flow (cooling effect) detectors and the smoke detector (Ref 26-16-51).
 E.  All circuit breakers for the equipment cooling system must be closed before a test is done.
 F.  The tests that follow include valve position checks. To find the position of the equipment cooling inboard supply valve, inboard exhaust valve, bypass valve, E6/E9 valve, smoke/override valve, and 3-way valve, look at the position indicator on the valve actuator. The position of the ground exhaust valve must be found by a visual check of the flapper position.
 TASK 21-58-00-705-001
 2.  Ground Test - Equipment Cooling_______________________________
 A.  General
 (1)  The ground test for the equipment cooling system commands the equipment cooling card to do a self-test and the equipment cooling system to go to the override mode. When the system is in the override mode, these conditions will occur:
 (a)  The supply and exhaust fans to stop.
 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
 21-58-00
 ALL  ú ú 12 Page 501 ú Feb 18/02 
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details. 
M03103
Pressure Correction
___________________  BAROMETRIC PRESSURE (IN. HG) 
A747-400MAINTENANCE MANUAL
Gage Pressure Correction Chart
Figure 501
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù.ú
 21-58-00
ALL  úú 02 Page 502 ú Jun 18/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details. 
1.  
Obtain local ambient barometric pressure (Pbar).
2.  
Measure E/E bay air temperature (Tbay).
3.  
Locate E/E bay temperature on left axis of table and follow row to the column corresponding to the Barometric pressure. Read the correction factor (Cf).
4.  
Calculate the corrected pressure (Pcor)as follows:
E/EPcor = P*Cf (Where: P is measured Baypressure)Temp (`F)Example 
P = 2.6 IN. H O
2
Pbar = 30.1 IN. HG 
Tbay = 46`F 
From table: (45`F/30.2 IN. HG) Cf = 0.95 
Pcor = 2.6 IN. H2O*0.95 = 2.47 IN. H2O 
____ For ambient conditions outside the range
NOTE: of the table, the correction factor mustbe calculated as follows: 
10  28.7  29.0  29.3  29.6  29.9  30.2  30.5  30.8  
0.93  0.92  0.91  0.90  0.89  0.88  0.87  0.86  
15  0.94  0.93  0.92  0.91  0.90  0.89  0.88  0.87  
20  0.95  0.94  0.93  0.92  0.91  0.90  0.89  0.88  
25  0.96  0.95  0.94  0.93  0.92  0.91  0.90  0.89  
30  0.97  0.96  0.95  0.94  0.93  0.92  0.91  0.90  
35  0.98  0.97  0.96  0.95  0.94  0.93  0.92  0.91  
40  0.99  0.98  0.97  0.96  0.95  0.94  0.93  0.92  
45  1.00  0.98  0.97  0.96  0.96  0.95  0.94  0.93  
 