 NOTE: If PASS shows, no failures occurred during the test.
____
 S 715-008
 (3)  If FAIL> shows:
 (a)  
Push the LSK that is adjacent to FAIL> to see the GROUND TEST MSG page for the failure.

 (b)  
Push the NEXT PAGE key until you find all the GROUND TEST MSG pages.

 (c)  
Make a list of all the CMCS messages, CMCS message numbers, and ATA numbers that show on the GROUND TEST MSG pages. 1) If the trim air regulating valve failed in the open

 position, make sure the CMCS message number 21167 shows.

 (d)  
Go to the CMCS Message Index of the Fault Isolation Manual (FIM) to find the corrective action for each CMCS message.


 E. Put the Airplane in its Usual Condition
 S 865-009
 (1)  Remove the electrical power, if it is not necessary
 (Ref 24-22-00/201).

 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-61-00
 ALL  ú ú 01F Page 502 ú Feb 10/94
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
 TASK 21-61-00-705-011
 3. Main Deck Cargo, Upper Deck, and Flight Deck Temperature Control Test
_____________________________________________________________________
 A. References
 (1)  
21-00-00/201, Air Conditioning System

 (2)  
24-22-00/201, Manual Control


 B. Access
 (1)  Location Zone
 221 Control Cabin, LH
 222 Control Cabin, RH

 C. Prepare for the Procedure
 S 865-012
 (1)  
Supply electrical power (AMM 24-22-00/201).

 S 865-013

 (2)  
Start the air conditioning packs (AMM 21-00-00/201).

 S 865-014

 (3)  
Close all the cabin doors.


 NOTE: You must do this step to minimize external influences on the
____ cabin temperature when the cabin temperature stabilizes.
 D. Procedure
 S 865-015
 (1)  
Push the ZONE SELECT switch on the cabin temperature selector in the upper deck until the zone display shows U (Upper Deck).

 S 865-016

 (2)
Push the COOLER switch until the target temperature is 19.

 S 865-017

 (3)  
Push the ZONE SELECT switch until the zone display shows C (Crew Rest Area).

 (4)
Push the COOLER switch until the target temperature is 19.

 S 715-019

 (5)  
Make sure on the EICAS ECS maintenance page that the zone U/D and C/R trim valve positions decrease (Move toward closed).


 S 865-018
 NOTE: The valves may take several minutes to move.
____
 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-61-00
 ALL  ú ú 01F Page 503 ú Feb 10/94
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400
MAINTENANCE MANUAL

 S 865-020
 (6)  Put the FLT DECK temperature selector on the overhead P5 panel to
 AUTO W.
 S 715-021
 (7)  Make sure that on the EICAS ECS maintenance page that the zone F/D
 trim valve position increases (Moves toward open).
 NOTE:____ The valve may take several minutes to move.

 S 715-022
 (8)  
Make sure that the F/D DUCT TEMP values increases.

 S 865-023

 (9)  
Put the MAIN DECK TEMP - AFT temperature selector on the overhead P5 panel to the AUTO W position.

 S 865-024

 (10)
 Push the ZONE SELECT switch on the cabin temperature selector until the zone display shows C.

 S 715-025

 (11)
 Make sure on the EICAS ECS maintenance page that the zone MAIN AFT trim valve positions (both L and R) increase (move toward open).


 NOTE: The valves may take several minutes to move.
____
 S 715-026
 (12)
 Make sure that the DUCT TEMP values for the zone MAIN AFT increases.

 S 865-027

 (13)
 Push the ZONE SELECT switch on the Cabin Temperature Selector until the zone display shows U.
 