RIGHT WHEEL WELL
SEE O
MASTER TRIM AIR SHUTOFF VALVE
FWD SEE R
AIR CONDITIONING EQUIPMENT BAY AND WHEEL WELL
AFT CARGO TRIM AIR MODULATION VALVE INBOARD BULKHEAD SEE P AFT CARGO TRIM AIR SHUTOFF VALVE
SEE Q
OUTBD FWD
RIGHT WHEEL WELL O
Zone Temperature Control System - Component Location
Figure 1 (Sheet 7)

D10143
 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-61-00
 ALL  ú ú 01F Page 8 ú Feb 10/95
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400
MAINTENANCE MANUAL

ZONE TRIM AIR MODULATION VALVE 
(EXAMPLE)  CARGO TRIM AIR SHUTOFF VALVE 
P  Q 

MASTER TRIM AIR SHUTOFF VALVE TRIM AIR PRESSURE SENSOR
R S
Zone Temperature Control System - Component Location
Figure 1 (Sheet 8)

 D10140
 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-61-00
 ALL  ú ú 01F Page 9 ú Feb 10/94
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A

747-400
MAINTENANCE MANUAL

FLIGHT DECK FLOW
REGULATING VALVE

SEE T
MIX BAY
FWD
VALVE
ACTUATOR

ELECTRICAL
MAIN DISTRIBUTION MANIFOLD
CONNECTOR CLAMP (2 LOCATIONS)
FLIGHT DECK FLOW REGULATING VALVE
FLIGHT DECK FLOW REGULATING VALVE T
Zone Temperature Control System - Component Location Figure 1 (Sheet 9)
G74027
 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-61-00
 ALL  ú ú 01F Page 10 ú Oct 10/97
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400
MAINTENANCE MANUAL

 C.  The MAIN DECK TEMP FWD AND MAIN DECK TEMP AFT selectors allow the flight crew to select the temperature of the main deck forward and aft cargo compartment. The selector has a MAN position to allow the cargo trim air modulating valves to be driven more open or more closed to increase or decrease cargo compartment temperature.
 D.  The LOWER LOBE TEMP FWD AND LOWER LOBE TEMP AFT selectors allow the flight crew to select the temperature of the lower lobe forward and aft cargo compartments. The selector has a MAN position to allow the trim air modulating valves to be driven more open or more closed to increase or decrease cargo compartment temperature.
 E.  The TRIM AIR switch allows the master trim air shutoff valve to be closed. When the switch is in the ON position, the valve is under automatic control.
 F.  The ZONE RST switch allows the master trim air shutoff valve to be reopened after it has been closed by a duct overheat. The switch contains a SYS FAULT light to alert the flight crew of the overheat.
 3.  Digital Cabin Temperature Selector (Fig. 1)
__________________________________
 A.  The digital cabin temperature selector located next to the lavatory door allows the cabin attendant to select the temperature of the Upper Deck and Crew Rest Area zones. The selector panel contains switches for zone temperature selection and a display to indicate the actual temperature and the target temperature of each specified zone.
 4.  Zone Temperature Controller (Fig. 1)
___________________________
 A.  A zone temperature controller (ZTC) controls and performs fault detection of cabin temperature control components for all phases of flight. The controller is located on the E2-4 electronics shelf in the main equipment center.
 B.  The zone temperature controller receives input from the following sources:
 (1)
Cabin Temperature Control Module

 (2)
Digital (Cabin Attendants') Cabin Temperature Selector

 (3)
Zone Temperature Sensors

 (4)
Duct Temperature Sensors

 (5)
ECS Miscellaneous Card

 (6)
Air/Ground Relay System

 (7)
Engine Speed Cards

 (8)
Master Trim Air Shutoff Valve

 (9)
 