 (a)  
Make sure that these lights on the P8-1 panel go off:
 1) the ENG 2 OVERHEAT light
 2) all of the lights in the engine-2 fire switch
 3) all of the lights in the APU fire switch.


 (b)  
Make sure these lights on the P7 panel go off: 1) AIRPLANES WITH OTHER THAN -98 FIRE DETECTION UNIT;


 the two FIRE WARN lights
 2) the two MASTER CAUTION lights
 3) the OVHT/DET annunciator.

 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-11-00
 ALL  ú ú 02A Page 503 ú Mar 15/99
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
737-300/400/500MAINTENANCE MANUAL
 (c)  AIRPLANES WITH OTHER THAN -98 FIRE DETECTION UNIT; make sure that you do not hear the alarm bell in the control cabin.
 S 865-013
 (8)  Close the FIRE PROTECTION DETECTION ENG 1 circuit breaker on the P6-2 panel.
 (a)  Make sure the FAULT light on the P8-1 panel goes off.
 S 865-014
 (9)  
Set the two OVHT DET switches on the P8-1 panel to the loop A position.

 S 865-015

 (10)
 Set and hold the TEST switch on the P8-1 panel to the OVHT/FIRE position.

 (a)  
Make sure these lights on the P8-1 panel come on:
 1) the ENG 1 OVERHEAT light
 2) the ENG 2 OVERHEAT light
 3) all of the lights in the engine-1 fire switch
 4) all of the lights in the engine-2 fire switch
 5) all of the lights in the APU fire switch.


 (b)  
Make sure these lights on the P7 panel come on:
 1) the two FIRE WARN lights
 2) the two MASTER CAUTION lights
 3) the OVHT/DET annunciator.


 (c)  
Make sure you hear the alarm bell in the control cabin.

 


 S 865-016
 (11) Release the TEST switch on the P8-1 panel.
 (a)  
Make sure these lights on the P8-1 panel go off:
 1) the ENG 1 OVERHEAT light
 2) the ENG 2 OVERHEAT light
 3) all of the lights in the engine-1 fire switch
 4) all of the lights in the engine-2 fire switch
 5) all of the lights in the APU fire switch.


 (b)  
Make sure these lights on the P7 panel go off:
 1) the two FIRE WARN lights
 2) the two MASTER CAUTION lights
 3) the OVHT/DET annunciator.


 (c)  
Make sure you do not hear the alarm bell in the control cabin.


 S 865-017
 (12)
 Set the two OVHT DET switches on the P8-1 panel to the loop B position.

 S 865-018

 (13)
 Set and hold the TEST switch on the P8-1 panel to the OVHT/FIRE position.


 (a)  Make sure these lights on the P8-1 panel come on:
 1) the ENG 1 OVERHEAT light

 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-11-00
 ALL  ú ú 03A Page 504 ú Jul 15/96
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A 737-300/400/500MAINTENANCE MANUAL
 2) the ENG 2 OVERHEAT light 3) all of the lights in the engine-1 fire switch 4) all of the lights in the engine-2 fire switch 5) all of the lights in the APU fire switch.
 (b)  
Make sure these lights on the P7 panel come on:
 1) the two FIRE WARN lights
 2) the two MASTER CAUTION lights
 3) the OVHT/DET annunciator.


 (c)  
Make sure you hear the alarm bell in the control cabin.


 S 865-019
 (14) Release the TEST switch on the P8-1 panel.
 (a)  
Make sure these lights on the P8-1 panel go off:
 1) the ENG 1 OVERHEAT light
 2) the ENG 2 OVERHEAT light
 3) all of the lights in the engine-1 fire switch
 4) all of the lights in the engine-2 fire switch
 5) all of the lights in the APU fire switch.


 (b)  
Make sure that these lights on the P7 panel go off:
 1) the two FIRE WARN lights
 2) the two MASTER CAUTION lights
 3) the OVHT/DET annunciator.


 (c)  
 