 (h)  
Connect the electrical connectors, D532 and D538, to the left and right switches, S2 and S5, respectively.

 (i)  
Push the TRIP RESET switch, on the P5-10 panel.

 (j)  
Make sure the PACK TRIP OFF lights go off.


 S 715-046
 (6)  Do this test of the 210°F ACM Turbine Inlet switches, S1 and S4:
 (a)  
Disconnect the electrical connectors, D530 and D536, from the left and right switches, S1 and S4, respectively.

 (b)  
Install a jumper wire between pin 1 and pin 2 of each switch electrical connector.

 (c)  
Make sure these lights come on: 1) Left and Right PACK TRIP OFF lights, on the P5-10 panel 2) MASTER CAUTION and AIR COND annunciator lights, on the P7

 panel

 (d)  
Push one of the MASTER CAUTION lights.

 (e)  
Make sure the AIR COND annuciator light and the MASTER CAUTION lights go off while the PACK TRIP OFF lights stay on.

 (f)  
Remove the jumper wire from pin 1 and pin 2 of each switch electrical connector.

 (g)  
Connect the electrical connectors, D530 and D536, to the left and right switches, S1 and S4, respectively.

 (h)  
Push the TRIP RESET switch, on the P5-10 panel.

 (i)  
Make sure the PACK TRIP OFF lights go off.


 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-51-00
 ALL  ú ú 01 Page 510 ú Jul 15/96
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
737-300/400/500MAINTENANCE MANUAL
 S 435-048
 (7)  
Connect the electrical connectors, D486 and D490, to the left and right pack valves, respectively.

 S 215-049

 (8)
Make sure the air mix valves move to the full COLD position.

 S 435-050

 (9)  
Connect the remaining electrical connectors which you removed from the left and right pack valves.

 S 865-051

 (10)
 Move the L PACK and R PACK switches to OFF.


 G. Put the Airplane Back to Its Usual Condition
 S 415-265
 (1)  
Close the bay doors for the air conditioning equipment.

 S 865-266

 (2)  
Remove the electrical power if it is not necessary (AMM 24-22-00/201).


 TASK 21-51-00-705-267
 4.  System Test - Air Cycle System - Pack Thermal Switch Test_________________________________________________________
 A. General
 (1)  This task has the steps to do a test of the 390 degree F ACM compressor discharge switches, S2 and S5, and the 210 degree F ACM turbine inlet switches, S1 and S4.
 B. Special Tools and Equipment
 (1)  Temp-Cal Probe Heater BH 3884-40 (attachment to
 Jet-Cal engine analyzer) or H294 Temp-Cal Thermal Switch Tester or H394 Temp-Cal Tester with adapter cable BH405
 BH24944 Heater Probe Kit (basic P/N)
 NOTE: This kit is necessary to use the
____ testers listed above. There are different dash number kits for specific airplane model and tester combinations. Please consult with supplier.
 Howell Instruments
 3479 West Vickery Blvd.
 Fort Worth, Texas 76107

 (2)  
Jumper wire

 (3)  
Voltmeter


 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 21-51-00
 ALL  ú ú 01 Page 511 ú Mar 12/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A

737-300/400/500
MAINTENANCE MANUAL

MACHINE AIR CYCLE BSEE 
SEE  A 
OVERHEAT SWITCH TURBINE INLET 

TURBO FAN 
VALVE 
SEE  F 
AIR CYCLE  TURBO FAN 
MACHINE  VALVE 
SEE  B  SEE  F 
FWD 
PACK 
VALVE 
SEE  C 

VISUAL 
INDICATOR 
LIMIT SWITCH 
CONNECTOR 

COMPRESSOR SOLENOID B
DRAIN PLUG  COMPRESSOR 
DISCHARGE 
OVERHEAT 
TURBINE  SIGHT  SWITCH 
 