 (8)  S 865-076Push the left master WARNING lights on the P72 panel.
 (9)  S 715-077Make sure that the master WARNING lights go off.
 S 715-078

 (10) Make sure that the alarm bell stops.

 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-14-00
 ALL  ú ú 08 Page 510 ú Oct 18/01
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
 S 865-079
 (11)
 Release the FIRE/OVHT TEST switch on the P5 panel.

 S 715-080

 (12)
 Make sure that the MAIN DECK CARGO warning light goes off.

 S 715-081

 (13)
 Make sure that the "CGO DET 1 MN DK" EICAS message shows.

 S 865-082

 (14)
 Open these circuit breakers:


 (a)  P7 Overhead Circuit Breaker Panel 1) 7H16 CARGO SMOKE - MAIN DECK ZN 1-8 DET A 2) 7H17 CARGO SMOKE - MAIN DECK ZN 1-8 DET B
 S 435-136
 (15)
 Connect the two electrical connectors DM5171 and DM5172 from the main deck cargo compartment.

 S 865-084

 (16)
 Close these circuit breakers:


 (a)  P7 Overhead Circuit Breaker Panel 1) 7H16 CARGO SMOKE - MAIN DECK ZN 1-8 DET A 2) 7H17 CARGO SMOKE - MAIN DECK ZN 1-8 DET B
 S 915-224
 (17) Use this table to do the test for the other smoke detectors: ~.................................................................
 |  CIRCUIT  | SMOKE DETECTOR |  EICAS MESSAGES  |
 |  BREAKER  |  CONNECTOR  ................................. ....
 |  |  |  WARNING  |  STATUS  |

 ................................................................... | 7H16, 7H17 | DM5173, DM5174 | FIRE MN DK FWD | CGO DET 2 MN DK | | 7H16, 7H17 | DM5175, DM5176 | FIRE MN DK FWD | CGO DET 3 MN DK | | 7H16, 7H17 | DM5177, DM5178 | FIRE MN DK FWD | CGO DET 4 MN DK | | 7H16, 7H17 | DM5179, DM5180 | FIRE MN DK FWD | CGO DET 5 MN DK | | 7H16, 7H17 | DM5181, DM5182 | FIRE MN DK MID | CGO DET 6 MN DK | | 7H16, 7H17 | DM5183, DM5184 | FIRE MN DK MID | CGO DET 7 MN DK | | 7H16, 7H17 | DM5185, DM5186 | FIRE MN DK MID | CGO DET 8 MN DK | | 7H18, 7H19 | DM5187, D51888 | FIRE MN DK MID | CGO DET 9 MN DK | | 7H18, 7H19 | DM5189, DM5190 | FIRE MN DK AFT | CGO DET 10 MN DK| | 7H18, 7H19 | DM5191, DM5192 | FIRE MN DK AFT | CGO DET 11 MN DK| | 7H18, 7H19 | DM5193, DM5194 | FIRE MN DK AFT | CGO DET 12 MN DK| | 7H18, 7H19 | DM5195, DM5196 | FIRE MN DK AFT | CGO DET 13 MN DK| | 7H18, 7H19 | DM5197, DM5198 | FIRE MN DK AFT | CGO DET 14 MN DK| | 7H18, 7H19 | DM5199, DM5200 | FIRE MN DK AFT | CGO DET 15 MN DK| | 7H18, 7H19 | DM5201, DM5202 | FIRE MN DK AFT | CGO DET 16 MN DK| 2............…................….................….................1
 EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú

 26-14-00
 ALL  ú ú 08 Page 511 ú Oct 15/98
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
 S 865-266
 (18)
 Make sure that these circuit breakers are closed:

 (a)  P7 Overhead Circuit Breaker Panel 1) 7H16 CARGO SMOKE - MAIN DECK ZN 1-8 DET A 2) 7H17 CARGO SMOKE - MAIN DECK ZN 1-8 DET B 3) 7H18 CARGO SMOKE - MAIN DECK ZN 9-16 DET A 4) 7H19 CARGO SMOKE - MAIN DECK ZN 9-16 DET B

 G.
One Disconnected Connector Smoke Detector Test


 S 865-261
 (1)  Open these circuit breakers:
 (a)  P7 Overhead Circuit Breaker Panel 1) 7H16 CARGO SMOKE - MAIN DECK ZN 1-8 DET A 2) 7H17 CARGO SMOKE - MAIN DECK ZN 1-8 DET B
 S 035-139
 (2)  
Disconnect one electrical connector DM5171 from the main deck cargo smoke detector.

 S 865-089

 (3)  
Close these circuit breakers:


 (a)  P7 Overhead Circuit Breaker Panel 1) 7H16 CARGO SMOKE - MAIN DECK ZN 1-8 DET A 2) 7H17 CARGO SMOKE - MAIN DECK ZN 1-8 DET B
 S 865-090
 (4)  
Push and hold the FIRE/OVHT TEST switch on the miscellaneous switch panel M7317 (P5).

 S 715-091

 (5)  
Look for these flight deck effects:

 (a)  
 