AIPC 26-16-01, Fig. 1
(3)
AIPC 26-16-01, Fig. 2
(4)
WDM 26-16-11 thru WDM 26-16-16
B. Access
(1) Location Zones 122 Forward Cargo Container Compartment Forward Half R.H. 142 Aft Cargo Compartment R.H.
C. Procedure
S 864-002
(1) Open these circuit breakers on the overhead circuit breaker panel, P7, and attach DO-NOT-CLOSE tags:
(a)
7H14, CARGO SMOKE DETECT LWR A
(b)
7H15, CARGO SMOKE DETECT LWR B
S 014-003
(2)
Get access to the applicable smoke detector (1) in the lower cargo compartment.
(3)
Remove the insulation around the smoke detectors where applicable.
S 014-023
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
26-16-01
ALL ú ú 06 Page 401 ú Oct 18/00
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400
MAINTENANCE MANUAL
Smoke Detector Installation
Figure 401
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
26-16-01
ALL ú ú 03 Page 402 ú Feb 10/94
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
E01261
A 747-400 MAINTENANCE MANUAL
(4) S 034-004Remove the applicable electrical connector (2) in the table that follows:
~................................................................ | CONNECTOR | DETECTOR | LOCATION | .................................................................. | DM7898 | M7898 | DET A - FWD CARGO SMOKE - ZONE 1 | | DM7899 | M7899 | DET B - FWD CARGO SMOKE - ZONE 1 | | DM7900 | M7900 | DET A - FWD CARGO SMOKE - ZONE 2 | | DM7901 | M7901 | DET B - FWD CARGO SMOKE - ZONE 2 | | DM4893 | M4893 | DET A - FWD CARGO SMOKE - ZONE 3 | | DM4894 | M4894 | DET B - FWD CARGO SMOKE - ZONE 3 | | DM4895 | M4895 | DET A - FWD CARGO SMOKE - ZONE 4 | | DM4896 | M4896 | DET B - FWD CARGO SMOKE - ZONE 4 | | DM4897 | M4897 | DET A - AFT CARGO SMOKE - ZONE 1 | | DM4898 | M4898 | DET B - AFT CARGO SMOKE - ZONE 1 | | DM4899 | M4899 | DET A - FWD CARGO SMOKE - ZONE 2 | | DM4900 | M4900 | DET B - FWD CARGO SMOKE - ZONE 2 | | DM7902 | M7902 | DET A - FWD CARGO SMOKE - ZONE 3 | | DM7903 | M7903 | DET B - FWD CARGO SMOKE - ZONE 3 | | DM7904 | M7904 | DET A - AFT CARGO SMOKE - ZONE 4 | | DM7905 | M7905 | DET B - AFT CARGO SMOKE - ZONE 4 | 2............….............….....................................1
(5) S 034-005Remove the clamp (6) and the sleeve (7) from the transition (5).
(6) S 034-006Remove the transition (5) and the clamp (4) from the air inlet (3).
(7) S 034-019Remove the transition (5) and the clamp (4) from the air outlet (10).
(8) S 034-007Remove the four screws (9) and washers (8) that hold the detector.
(9) S 024-020Remove the detector (1).
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
26-16-01
ALL ú ú 03 Page 403 ú Oct 10/93
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
TASK 26-16-01-404-008
3. Install the Smoke Detector (Fig. 401)__________________________
A. Parts
~...................................................................... | AMM | | AIPC | ................. ............................ | FIG | ITEM | NOMENCLATURE | SUBJECT | FIG | ITEM | ........................................................................ | 401 | 1 | Detector | 26-16-01 | 05 | 15 | | | 9 | Screw | | | 20 | 2......…........…...........................…..........….....….........1