R  (Ref. Fig. 002A) 
R  **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 401-499, 
R  The power supply provides the galley assemblies with 115 V AC through the 
R  three phase normal busbars 1XP and 2XP. Six triple core wires (feeders A to 
R  F) distribute the power to terminal blocks in the forward and aft galley 
R  area. Vendor wiring distributes the power to the galley units. The wiring is 
R  connected to the terminal blocks by the electrical connector. 
R  The maximum available load for all galleys is 50 KVA. The load is 
R  distributed as follows: 
R  - Network 1 = feeder A, B and E with 30 KVA, 

R 1EFF : 001-049, 051-099, 101-149, 151-199, 1 24-56-00Page 4 1201-299, 401-499, 1Aug 01/05 1 1 1CES 1


R  - Network 2 = feeder C, D and F with 20 KVA. 
R  Circuit breakers protect the feeders. Power contactors switch the power.
 4. Operation/Control & Ind_______________________ 
R  The power contactors for the galleys are controlled through control relays 
R  as follows: 
R  With the APU generator running or with external power supplied you can 
R  supply all feeders with power (on the ground). With both engine driven 
R  generators running, you can supply all feeders with power (on the ground or 
R  in flight). With only engine 1 driven generator running, only feeders B and 
R  D is supplied. Feeders A, C, E and F are shed automatically (on the ground 
R  or in flight). You can manually shed all the feeders to the galley with the 
R  pushbutton switch 2XA GALLEY OFF in the cockpit (on the overhead panel 
R  35VU).
 **ON A/C 301-399,
 3. System Description__________________ 
R  (Ref. Fig. 002B) 
R  The power supply provides the galley assemblies with 115 V AC through the 
R  three phase normal busbars 1XP and 2XP. Six triple core wires (feeders A, C, 
R  D, E and F) distribute the power to terminal blocks in the forward, mid and 
R  aft galley area. Vendor wiring distributes the power to the galley units. 
R  The wiring is connected to the terminal blocks with cable lugs. 
R  The maximum available load for all galleys is 70 KVA. The load is 
R  distributed as follows: 
R  - FWD feeder = 40 KVA or 25 KVA or 25 KVA, 
R  - MID feeder = 0 KVA or 15 KVA or 0 KVA, 
R  - AFT feeder = 30 KVA or 30 KVA or 45 KVA. 
R  Circuit breakers protect the feeders. Power contactors switch the power.
 4. Operation/Control & Ind_______________________ 
R  The power contactors for the galleys are controlled through control relays 
R  as follows: 
R  With the APU generator running or with external power supplied you can 
R  supply all feeders with power (on the ground). With both engine driven 
R  generators running, you can supply all feeders with power (on the ground or 
R  in flight). With only engine 1 driven generator running, only feeder D is 
R  supplied. Feeders A, C, E and F are shed automatically (on the ground or in 
R  flight). You can manually shed all the feeders to the galley with the 
R  pushbutton switch 2XA GALLEY OFF in the cockpit (on the overhead panel 
R  35VU). 

R 1EFF : ALL 1 24-56-00Page 5 1 1 Aug 01/05 1 1 1CES 1


 Galley Power Supply and Distribution - Schematic Figure 002 (SHEET 1)
R 1EFF : 001-049, 101-149, 151-199, 211-299, 1 24-56-00Page 6 1401-499, 1Aug 01/05 1 1 1CES 1


 Galley Power Supply and Distribution - Schematic Figure 002 (SHEET 2)
R 1EFF : 001-049, 101-149, 151-199, 211-299, 1 24-56-00Page 7 1401-499, 1Aug 01/05 1 1 1CES 1


 Galley Power Supply and Distribution - Schematic
 Figure 002A (SHEET 1)

R 1EFF : 051-099, 201-210, 1 24-56-00Page 8 1 1 Aug 01/05 1 1 1CES 1


 Galley Power Supply and Distribution - Schematic
 Figure 002A (SHEET 2)

R 1EFF : 051-099, 201-210, 1 24-56-00Page 9 1 1 Aug 01/05 1 1 1CES 1R Galley Power Supply and Distribution - Schematic R Figure 002B (SHEET 1)


 1EFF : 301-399, 1 24-56-00Page 10 1 1 May 01/04 1 1 1CES 1R Galley Power Supply and Distribution - Schematic R Figure 002B (SHEET 2)


 1EFF : 301-399, 1 24-56-00Page 11 1 1 May 01/04 1 1 1CES 1 GALLEY SUPPLY - DEACTIVATION/REACTIVATION