(b)
Open these circuit breakers and attach the DO-NOT-CLOSE tags:
NOTE: Open these circuit breakers when you remove GCU 1.
____
1) On the P180 or P180-1 panel:
a) C8 or M4, GCU 1
b) B25, GCU 1 ALT
2) On the P514 panel:
a) GCU 1 PHASE C SYNCH BUS
(c) Open these circuit breakers and attach the DO-NOT-CLOSE tags:
NOTE: Open these circuit breakers when you remove GCU 2.
____
1) On the P180 or P180-1 panel:
a) C9 or M5, GCU 2
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
24-23-01
ALL ú ú 02 Page 403 ú Oct 10/95
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400 MAINTENANCE MANUAL
b) B26, GCU 2 ALT 2) On the P614 panel: a) GCU 2 PHASE C SYNC BUS
(d) Open these circuit breakers and attach the DO-NOT-CLOSE tags:
NOTE: Open these circuit breakers when you remove GCU 3.
____
1) On the P180 or P180-1 panel: a) C10 or M6, GCU 3 b) B27, GCU 3 ALT
2) On the P515 panel: a) GCU 3 PHASE C SYNC BUS
(e) Open these circuit breakers and attach the DO-NOT-CLOSE tags:
NOTE: Open these circuit breakers when you remove GCU 4.
____
1) On the P180 or P180-1 panel: a) C11 or M7, GCU 4 b) B28, GCU 4 ALT
2) On the P615 panel: a) GCU 4 PHASE C SYNCH BUS
D. Remove the Control Unit
S 864-016
(1)
Make sure the BATTERY switch, on the P5 panel, is set to OFF and attach a DO-NOT-OPERATE tag.
S 024-003
(2)
Remove the applicable GCU or BCU from the E/E rack (AMM 20-11-22/401).
TASK 24-23-01-404-004
3. Generator and Bus Control Unit Installation (Fig. 401)
___________________________________________
A. References
(1) AMM 20-11-22/401 Rack-Mounted Electrical/Electronic Module
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
24-23-01
ALL ú ú 02 Page 404 ú Oct 10/94
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
747-400
MAINTENANCE MANUAL
(2)
AMM 24-22-00/201, Manual Control
(3)
AMM 45-10-00/201, Central Maintenance Computer System
(4)
AIPC 24-23-01, Fig. 20
(5)
AIPC 24-23-01, Fig. 30
(6)
WDM 24-11-11 thru WDM 24-11-14, WDM 24-21-12, WDM 24-21-22, WDM 24-21-32, WDM 24-21-42, WDM 24-22-11 thru WDM 24-22-74, WDM 24-23-11 thru WDM 24-23-22, WDM 24-27-51 thru WDM 24-27-52, WDM 24-41-12 thru WDM 24-41-23
(7)
SSM 24-11-01 thru SSM 24-11-04, SSM 24-21-01 thru SSM 24-21-04, SSM 24-22-01 thru SSM 24-22-07, SSM 24-23-01 thru SSM 24-23-02, SSM 24-23-04, SSM 24-27-01 thru SSM 24-27-07, SSM 24-32-02, SSM 24-34-01 thru SSM 24-34-03, SSM 24-41-01 thru SSM 24-41-02
B.
Access
(1)
Location Zone
117 Electrical and Electronics Compartment, LH
118 Electrical and Electronics Compartment, RH
C.
Install the Generator Control Unit or the Bus Control Unit
S 424-005
(1)
Install the applicable GCU or BCU in the E/E rack
(AMM 20-11-22/401).
S 864-017
(2)
Remove the DO-NOT-OPERATE tag from the BATTERY switch.