2._The XPOF2 setpoint is 437.5 |2.5 Hz. If this condition persists for 30 |10 milliseconds, XPOF2 protective function deenergizes the XPC, GSSR, GSTR, and GR-XP. XPOF2 is intended to protect against severe fault conditions.
4) Underfrequency (UF) Protection
a) Underfrequency protection is accomplished by sampling phase C of the external power voltage. There are two underfrequency setpoints: underfrequency 1 (XPUF1) and underfrequency 2 (XPUF2).
1._The XPUF1 setpoint is 372.5 |2.5 Hz. If this condition pesists for 1.2 |0.4 seconds, the XPC, GSSR, GSTR, and GHR-XP are de-energized.
2._The XPUF2 setpoint is 352.5 |2.5 Hz. If this condition persists for 150 |50 milliseconds, the XPC, GSSR, GSTR, and GHR-XP are de-energized. XPUF2 is intended to protect against severe fault conditions.
5) Phase Sequence (o SEQ) Protection
a) The external power phase sequence protection indicates a phase sequence "ok" when the external power plug is connected and the phase sequence is A-B-C.
(o) Synchronizing Bus Faults 1) Differential Current Protection (DP) a) The DP is accomplished through the differential phase current transfromers (DPCTs). A DP fault condition exists when a minimum differential current of 30 |5 amps is detected for a frequency between 370 and 430 Hz for 175 |25 milliseconds. The DP is handled by CPU differential current protection (DP CPU) or redundant differential current protection (RDNT DP). b) CPU Differential Current Protection (DP CPU). The hardware circuit for the DP CPU inputs to the CPU the level of the differential current detected. The CPU compares this differential current level to a threshold level set in software. If it is greater or equal to the threshold level, the CPU begins the time delay and inhibits the redundant differential current protection (RDNT DP).
c) The hardware circuit for the DP CPU inputs to the CPU the level of the differential current detected. The CPU compares this differential current level to a threshold level set in software. If it is greater or equal to the threshold level, the CPU begins the time delay and inhibits the redundant differential current protection (RDNT DP).