R  **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 
 (2) Flow Control Reference 
 The crew can select the flow control reference to 80 %, 100 % or 120 
 % of the nominal value. The selected values are modified under the 
 conditions listed below: 
 - during APU operation, the zone controller 8HK receives the discrete 
 APU bleed-valve open signal and resets the flow reference to 120 %. 
 This overrides any other selection or commands, (The APU control 
 and APU demand signals control the APU bleed air flow). 
 - if 80 % is selected, the controller can increase the flow reference 
 up to 100 % when the cooling demand is not met. This means one zone 
 duct demand temperature has reached predetermined limit value. 
 - when there is only one pack operating the controller 7HH (27HH) for 
 that pack will increase the flow reference to 120 %.  
R  
R  **ON A/C 301-399, 
 (2) Flow Control Reference 
 The crew can select the flow control reference to 80 % (ECON) of the 
 nominal value. The selected values are modified under the conditions 
 listed below: 
 - during APU operation, the zone controller 8HK receives the discrete 
 APU bleed-valve open signal and resets the flow reference to 120 % 
 to command the FCV fully open. This overrides any other selection 
 or commands, (The APU control and APU demand signals control the 
 APU bleed air flow). 
 - if 80 % is selected, the controller can increase the flow reference 
 up to 100 % when the cooling demand is not met. This means one zone 
 duct demand temperature has reached predetermined limit value. 
 - when there is only one pack operating the controller 7HH (27HH) for 
 that pack will increase the flow reference to 120 %.  
R  **ON A/C 401-499,  
R  (2) Flow Control Reference  
R  The crew can select the flow control reference to 80 %, 100 % or 120  
R  % of the nominal value. The pack flow demand reference signal is  
R  computed by ACSC 1 and ACSC 2 separately. In case of special  
R  conditions the ACSC generates an other flow demand than the one  
R  selected by the pilot in order to fulfill the environmental  
R  temperature and flow requirements: 
R 1EFF : ALL 1 21-63-00Page 76 1 1 Aug 01/05 1 1 1CES 1
R  - during APU operation, the ACSC's receive the discrete APU  
R  bleed-valve open signal and reset the flow reference to 120 %. This  
R  overrides any other selection or commands, (The APU control and APU  
R  demand signals control the APU bleed air flow).  
R  - if 80 % is selected, the ACSC's can increase the flow reference up  
R  to 100 % when the cooling demand is not met. This means one zone  
R  duct demand temperature has reached predetermined limit value.  
R  - when there is only one pack operating the controller 47HH (57HH)  
R  for that pack will increase the flow reference to 120 %.  
R  **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399, 
 (3) APU Demand Signal 
 A signal from the zone controller 8HK can increase the APU bleed air 
 flow output if any selected zone temperature is not met. The demand 
 signal is 0% for most normal operating conditions. This increases 
 