26-12-00-991-302 Fig. 603 26-12-00-991-303 Fig. 604
 3. Job Set-up
__________ Subtask 26-12-00-941-052
 A. Safety Precautions
 (1)
 On the center pedestal, on the ENG panel 115VU:

 (a) Put a warning notice to tell persons not to start the engine 1(2).

 (2)
 Make sure that the engine 1(2) has been shutdown for at least 5 minutes.

 (3)
 On the overhead maintenance panel 50VU:

 (a)
 Make sure that the ON legend of the ENG/FADEC GND PWR/1(2) pushbutton switch is off.

 (b)
 Install a warning notice to tell persons not to energize the FADEC 1(2).

 


 Subtask 26-12-00-865-052
 B. Open, safety and tag this(these) circuit breaker(s):
 -------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------49VU ENGINE/2/FIRE DET/LOOP B 8WD2 A07
 49VU ENGINE/1/FIRE DET/LOOP A 7WD1 A06 121VU ENGINE/ENG2/FIRE DET/LOOP A 7WD2 Q39 121VU ENGINE/ENG1/FIRE DET/LOOP B 8WD1 Q38 Subtask 26-12-00-010-054


 C. Get Access
 (1) Open the fan cowl doors: (Ref. TASK 71-13-00-010-040)
 FOR 1000EM1
 437AL, 438AR
 FOR 1000EM2
 447AL, 448AR

 (2)
 Put the access platform in position. Subtask 26-12-00-040-053

 D.
 Make the thrust reverser unserviceable (Ref. TASK 78-30-00-481-041). Subtask 26-12-00-010-055


 E. Open the thrust reverser doors (Ref. TASK 78-36-00-010-040):
 FOR 1000EM1
 451AL, 452AR
 FOR 1000EM2
 461AL, 462AR

 4. Procedure
_________ Subtask 26-12-00-210-056
 A. Visual Inspection of Pylon Fire-Detection Loops
 (Ref. Fig. 601/TASK 26-12-00-991-300)

 (1)
 Make sure that the straight length of the sensing element from the responder head welding is 20 mm (0.7874 in.) minimum (see detail A).

 (2)
 Make sure that the radius of the sensing element is 9.5 mm (0.3740 in.) minimum.

 (3)
 Make sure that the minimum distance between the sensing element and its support is 6 mm (0.2362 in.) (see detail B).

 (4)
 Make sure that the maximum distance between the ends of the two sensing elements and the last clamp is 25.4 mm (1.0000 in.) (see detail C).

 (5)
 Make sure that all the bushes are in good condition. If not, replace them (Ref. TASK 26-12-16-000-001) (see details B and C).

 (6)
 Make sure that there is no damage or chafing on the fire detectors, the rail assemblies and the related brackets.

 (7)
 Make sure that there is no damage or chafing on the detection harness insulations to prevent short circuit.

 


 Pylon Fire Detectors
 Figure 601/TASK 26-12-00-991-300
 1EFF :  ALL  1  26-12-00 Page 604 
1  1  Aug 01/00
 1  1
 1CES  1

 

 Subtask 26-12-00-210-057
 B. Visual Inspection of Fan Fire-Detection Loops
 (Ref. Fig. 602/TASK 26-12-00-991-301)

 (1)
 Make sure that the straight length of the sensing element from the responder head welding is 20 mm (0.7874 in.) minimum.

 (2)
 Make sure that the minimum distance between the sensing element and its support is 6 mm (0.2362 in.).

 (3)
 Make sure that all the grommets are in good condition. If not, replace them (Ref. TASK 26-12-15-000-042) (see detail B).

 (4)
 Make sure that there is no damage or chafing on the fire detectors, the rail assemblies and the related brackets.

 (5)
 Make sure that there is no damage or chafing on the detection harness insulations to prevent short circuit.


 Subtask 26-12-00-210-058
 C. Visual Inspection of Core Fire-Detection Loops
 (Ref. Fig. 603/TASK 26-12-00-991-302, 604/TASK 26-12-00-991-303)

 (1)
 Make sure that the straight length of the sensing element from the responder head welding is 20 mm (0.7874 in.) minimum.

 (2)
 Make sure that the radius of the sensing element is 9 mm (0.3543 in.) minimum.

 (3)
 Make sure that the maximum distance between the ends of the two sensing elements and the last clamp is 25.4 mm (1.0000 in.).

 (4)
 Make sure that the minimum distance between the sensing element and its support is 6 mm (0.2362 in.).

 (5)
 Make sure that all the bushes are in good condition. If not, replace them (Ref. TASK 26-12-17-000-041).
 