3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
106VU ESS TR/SPLY 4PE C01
B. Test Do the operational test of the central warning systems (SDAC) (Ref. AMM TASK 31-50-00-710-001).
4. Fault Isolation
_______________
A. If the test gives the maintenance message SDAC 1 : NO TR ESS CURRENT 1PE:
- replace the SDAC-1 (1WV1), (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the SDAC 1 (1WV1) pins AB/14E, 14F to the first terminal block , (Ref. ASM 24-34/01).
B. Do the test given in Para. 3.B.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : ALL ∞∞31-54-00∞∞∞∞∞∞∞∞∞∞Page 283
Aug 01/05 CES Loss of the ESS TRU CURRENT Bus of the SDAC 2
1. Possible Causes
_______________
- SDAC-2 (1WV2)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 31-50-00-710-001 Ground Scanning of the Central Warning System
AMM 31-55-34-000-001 Removal of the SDAC (1WV1,1WV2)
AMM 31-55-34-400-001 Installation of the SDAC (1WV1,1WV2)
ASM 24-34/01
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
106VU ESS TR/SPLY 4PE C01
B. Test Do the operational test of the central warning systems (SDAC) (Ref. AMM TASK 31-50-00-710-001).
4. Fault Isolation
_______________
A. If the test gives the maintenance message SDAC 2 : NO TR ESS CURRENT 1PE:
- replace the SDAC-2 (1WV2), (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the SDAC 2 (1WV2) pins AB/14E, 14F to the first terminal block , (Ref. ASM 24-34/01).
B. Do the test given in Para. 3.B.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : ALL ∞∞31-54-00∞∞∞∞∞∞∞∞∞∞Page 284
Aug 01/05 CES Loss of the ESS TRU VOLTAGE Input of the SDAC 1
1. Possible Causes
_______________
- SDAC-1 (1WV1)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 31-50-00-710-001 Ground Scanning of the Central Warning System
AMM 31-55-34-000-001 Removal of the SDAC (1WV1,1WV2)
AMM 31-55-34-400-001 Installation of the SDAC (1WV1,1WV2)
ASM 24-34/01
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------
106VU ESS TR/SPLY 4PE C01
B. Test Do the operational test of the central warning systems (SDAC) (Ref. AMM TASK 31-50-00-710-001).
4. Fault Isolation
_______________
A. If the test gives the maintenance message SDAC 1 : NO TR ESS VOLTAGE 1PE:
- replace the SDAC-1 (1WV1), (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the SDAC 1 (1WV1) pin AB/7K to the first terminal block , (Ref. ASM 24-34/01).
B. Do the test given in Para. 3.B.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-54-00∞∞∞∞∞∞∞∞∞∞Page 285