1. Possible Causes
_______________
- CFDIU (1TW)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 31-32-00-869-002 Procedure for Class 3 Faults Reading
AMM 31-32-34-000-001 Removal of the CFDIU (1TW)
AMM 31-32-34-400-001 Installation of the CFDIU (1TW)
ASM 31-32/04
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------49VU AIR BLEED/ENG 1/CTL 3HA1 D12 49VU AIR BLEED/ENG 1/MONG 2HA1 D11
B. Test On the CFDS MENU page, get access to the AVIONICS STATUS page (Ref. AMM TASK 31-32-00-869-002).
4. Fault Isolation
_______________
A. If the test gives the maintenance message:
NO BMC 1 DATA:
- replace the CFDIU (1TW), (Ref. AMM TASK 31-32-34-000-001) and (Ref. AMM TASK 31-32-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the CFDIU (1TW) pins AA/7D, 7E to the first terminal block , (Ref. ASM 31-32/04).
B. Do the test given in Para. 3.B.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-32-00∞∞∞∞∞∞∞∞∞∞Page 253
Nov 01/04R CES
Loss of the Bus Output from the BMC 2 to the CFDIU
1. Possible Causes
_______________
- CFDIU (1TW)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 31-32-00-869-002 Procedure for Class 3 Faults Reading
AMM 31-32-34-000-001 Removal of the CFDIU (1TW)
AMM 31-32-34-400-001 Installation of the CFDIU (1TW)
ASM 31-32/05
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------122VU AIR BLEED/ENG 2/CTL 3HA2 Z23 122VU AIR BLEED/ENG 2/MONG 2HA2 Z22
B. Test On the CFDS MENU page, get access to the AVIONICS STATUS page (Ref. AMM TASK 31-32-00-869-002).
4. Fault Isolation
_______________
A. If the test gives the maintenance message:
NO BMC 2 DATA:
- replace the CFDIU (1TW), (Ref. AMM TASK 31-32-34-000-001) and (Ref. AMM TASK 31-32-34-400-001).
(1) If the fault continues:
- do a check and repair the wiring from the CFDIU (1TW) pins AB/7F, 7G to the first terminal block , (Ref. ASM 31-32/05).
B. Do the test given in Para. 3.B.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : ALL ∞∞31-32-00∞∞∞∞∞∞∞∞∞∞Page 254
Nov 01/04 CES
R **ON A/C 001-049, 051-099, 101-105, 151-199, 201-299,
TASK 31-32-00-810-848
Loss of the Output Bus from the Vacuum System Controller or the CIDS Director
(s) to the CFDIU
1. Possible Causes
_______________
- CFDIU (1TW)
- CONTROLLER-VACUUM SYSTEM (31MG)
- wiring from the CFDIU (1TW) to the vacuum system controller (31MG)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 31-32-00-740-009 Read the AVIONICS STATUS on the MCDU AMM 31-32-34-000-001 Removal of the CFDIU (1TW) AMM 31-32-34-400-001 Installation of the CFDIU (1TW) AMM 38-31-34-000-001 Removal of the Vacuum System Controller 31MG AMM 38-31-34-400-001 Installation of the Vacuum System Controller 31MG ASM 31-32/03
3. Fault Confirmation
__________________