a mounting bracket,
-
a discharge tube with a fusible plug,
-
a pressure gage,
-an identification label. The spherical container is made of brass and has a diameter of approximately 60 mm (2.3622 in.). The mounting bracket, the discharge tube and the fill port are attached to the container. The fusible plug installed in the end of the discharge tube seals the tube and keeps the extinguisher agent in the container. The container is charged with the extinguisher agent through the fill valve in the fill port. The extinguisher agent also pressurizes the container. The pressure gage is installed on the fill port after the container is charged. The identification label bonded to the container shows:
-
the part number,
-
the serial number,
-
the date of manufacture,
-
the extinguisher agent type,
-
the total weight of the extinguisher.
**ON A/C 001-049, 051-099, 101-105, 151-199, 201-210,
4. Operation
_________ The lavatory fire-extinguishing system is completely automatic and self-contained. A fire or overheat condition opens the release mechanism. When the temperature in the waste paper-bin area is approx. 79 DEG.C (174.20 DEG.F) the fusible material in the tip of the discharge tube melts. The lavatory fire extinguisher then discharges completely within 3 to 15 s. Each unit weighs 0.454 kg max. It stores and discharges 100 to 130 g of Halon 1301 into the waste paper bin to extinguish the fire.
R **ON A/C 106-149, 211-299, 301-399, 401-499,
4. Operation
_________ The lavatory fire-extinguishing system is completely automatic and self-contained. A fire or overheat condition opens the release mechanism. When the temperature in the waste paper-bin area is approx. 79 DEG.C (174.20 DEG.F) the fusible material in the tip of the discharge tube melts. The lavatory fire extinguisher then discharges completely within 3 to 15 s. Each unit weighs 0.360 kg max. It stores and discharges 120 g of agent FE36 into the waste paper bin to extinguish the fire.
R 1EFF : 106-149, 211-299, 301-399, 401-499, 1 26-25-00Page 3 1 1 Aug 01/05 1 1 1CES 1
LAVATORY FIRE EXTINGUISHING - MAINTENANCE PRACTICES
___________________________________________________
R TASK 26-25-00-600-001
R General Visual Inspection of Lavatory Fire Extinguisher for Signs of
R Leakage/Discharge
R NOTE : To make sure that the fire extinguisher bottle is serviceable.____
R 1. Reason for the Job__________________
R Refer to the MPD TASK: 262541-01
R 2. Job Set-up Information______________________
R A. Referenced Information
R -------------------------------------------------------------------------------
R REFERENCE DESIGNATION
R -------------------------------------------------------------------------------
R 26-25-00-600-002 Weight Check of the Lavatory Fire-Extinguisher
R Bottles
R 26-25-00-991-001 Fig. 201
R 3. Job Set-up__________
R Subtask 26-25-00-010-050
R A. Open the service door.
R 4. Procedure_________
R (Ref. Fig. 201/TASK 26-25-00-991-001)
R Subtask 26-25-00-210-051
R A. Check the Lavatory Fire-Extinguisher Bottle
R (1) Read the pressure gage of the fire-extinguisher bottle. Make sure
R that the indication is in the green sector of the gage.
R (2) Examine the fire extinguisher bottle for dents or scratches.
R (3) Examine the fire extinguisher arm/arms for pinches or damages.
Lavatory Fire Extinguisher Figure 201/TASK 26-25-00-991-001
1EFF : 1 1R 1CES ALL 1 11 1 26-25-00 Page 202 Aug 01/05
R (4) Replace the fire extinguisher if any of the conditions in steps (2)
R thru (3) are shown (Ref. TASK 26-25-00-600-002).
R 5. Close-up________
R Subtask 26-25-00-410-050
R A. Close Access
R (1) Make sure that the work area is clean and clear of tool(s) and other
R items.
R (2) Close the service door.
TASK 26-25-00-600-002
Weight Check of the Lavatory Fire-Extinguisher Bottles
1.
Reason for the Job
__________________
Refer to the MPD TASK: 262541-02
2.
Job Set-up Information
______________________
Not Applicable
3.