R 1EFF : 401-499, 1 21-51-00Page 56 1 1 Aug 01/05 1 1 1CES 1
R (5) Operation with Failures
R (a) Single Pack Failure
R When the PACK FLOW selector is set to the NORM or LO position and
R there is a failure in one pack, the ACSC modulates the other pack
R to the 120% (HI) mode. Thus the flow control valve is commanded
R to the fully open position.
R (b) Engine Fire
R If there is an engine fire, and you push the applicable FIRE
R pushbutton switch, the respective flow control valve closes. This
R stops the hot bleed air flow in order to prevent damage to the
R components of the air conditioning system and to prevent entry of
R smoke into the cabin.
R (c) Ditching
R In case of landing on water the DITCHING pushbutton switch must
R be pushed. This closes the flow control valves which prevents the
R entry of water into the cabin through the air conditioning
R system.
R (d) Air-Cycle Machine Compressor Overheat
R If the compressor of an air-cycle machine exceeds 215 deg.C
R (419.00 deg.F), the ACSC and flow control valve will start to
R reduce the pack flow independent of the flow demand till the
R minimum flow demand is reached.
R When the compressor temperature reaches 260 deg.C (500.00 deg.F)
R (overheats) on ground, the ACSC will shut off the pack (flow
R control valve is closed).
R (e) Pack Shut-down in the Engine-Start Sequence
R In the engine-start sequence (the EIU gives an engine rpm-signal
R of N1<50%), normally both air-packs close.
R To prevent the complete pack shut-down in flight because of a
R wrong EIU-signal, the crossbleed valve indication relay 7HV
R monitors the position of the Cross Bleed Valve (CBV) 6HV:
R - If the CBV is in the closed position, only one pack instead of