- CONT-AIR COND SYSTEM 2 (57HH)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 21-61-00-710-001 Operational Test of the Pack Temperature-Control System AMM 21-61-34-000-002 Removal of the Air-Conditioning System Controller (47HH, 57HH) AMM 21-61-34-400-002 Installation of the Air-Conditioning System Controller (47HH, 57HH) ASM 21-61/03
3. Fault Confirmation
__________________
A. Do the operational test of the pack temperature-control system (Ref. AMM TASK 21-61-00-710-001).
4. Fault Isolation
_______________
A. If the test gives the maintenance message ACSC1(47HH)/ACSC2(57HH) /WRG: ACSC1 BUSES TO ACSC2:
- do a check and repair the wiring (Ref. ASM 21-61/03) from:
- the ACSC1 (47HH) connector AA/5E to the ACSC2 (57HH) connector AA/3F,
- the ACSC1 (47HH) connector AA/5F to the ACSC2 (57HH) connector AA/3G,
- the ACSC1 (47HH) connector AA/6E to the ACSC2 (57HH) connector AA/4E,
- the ACSC1 (47HH) connector AA/6F to the ACSC2 (57HH) connector AA/4F.
(1) If the fault continues:
- replace the CONT-AIR COND SYSTEM 1 (47HH) (Ref. AMM TASK 21-61-34-000-002) and (Ref. AMM TASK 21-61-34-400-002).
(2) If the fault continues:
- replace the CONT-AIR COND SYSTEM 2 (57HH) (Ref. AMM TASK 21-61-34-000-002) and (Ref. AMM TASK 21-61-34-400-002).
B. Do the test as given in the Para. 3.A.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 401-499, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page B227
Aug 01/05 CES
TASK 21-61-00-810-896
Pack 1 Discharge Pressure Sensor Fault
1. Possible Causes_______________
- P1 PACK DISCH PRESS SENSOR (14HH)
- wiring
2. Job Set-up Information______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 21-61-00-710-001 Operational Test of the Pack Temperature-Control System
AMM 21-61-14-000-001 Removal of the Pack Discharge Pressure Sensor (14HH,20HH)
AMM 21-61-14-400-001 Installation of the Pack Discharge Pressure Sensor (14HH, 20HH)
ASM 21-61/04
3. Fault Confirmation__________________
A. Do the operational test of the pack temperature-control system (Ref. AMM TASK 21-61-00-710-001).
4. Fault Isolation_______________
A. If the test gives the maintenance message P1 DISCHARGE PRESS
SENSOR(14HH):
- replace the P1 PACK DISCH PRESS SENSOR (14HH) (Ref. AMM TASK 21-61-14-000-001) and (Ref. AMM TASK 21-61-14-400-001).
(1) If the fault continues:
- do a check of the wiring (Ref. ASM 21-61/04) from:
- the SENSOR (14HH) to the ACSC 1 (47HH) and,
- the SENSOR (14HH) to ground.
B. Do the test as given in the Para. 3.A.
TASK 21-61-00-810-897
Pack 2 Discharge Pressure Sensor Fault
1. Possible Causes_______________
- P2 PACK DISCH PRESS SENSOR (20HH)
- wiring
2. Job Set-up Information______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 21-61-00-710-001 Operational Test of the Pack Temperature-Control System
AMM 21-61-14-000-001 Removal of the Pack Discharge Pressure Sensor (14HH,20HH)
AMM 21-61-14-400-001 Installation of the Pack Discharge Pressure Sensor (14HH, 20HH)
ASM 21-61/02
3. Fault Confirmation__________________
A. Do the operational test of the pack temperature-control system (Ref. AMM TASK 21-61-00-710-001).
4. Fault Isolation_______________
A. If the test gives the maintenance message P2 DISCHARGE PRESS
SENSOR(20HH):
- replace the P2 PACK DISCH PRESS SENSOR (20HH) (Ref. AMM TASK 21-61-14-000-001) and (Ref. AMM TASK 21-61-14-400-001).
(1) If the fault continues:
- do a check of the wiring (Ref. ASM 21-61/02) from: