+ 18 13340 +/- 5 %
+ 25 10000 +/- 5 %
+ 30 8197 +/- 5 %
+ 40 5598 +/- 5 %
+ 50 3903 +/- 5 %
(1) If the resistance values are out of the specified limits:
- replace the SENSOR-DUCT TEMPERATURE,AFT CABIN (17HK) (Ref. AMM TASK 21-63-15-000-001) and (Ref. AMM TASK 21-63-15-400-001).
(2) If the resistance values are in the specified limits:
- do a check and repair the wiring (Ref. ASM 21-63/03) from:
- the SENSOR-DUCT TEMPERATURE,AFT CABIN (17HK) to the ZC (8HK) and,
- the SENSOR-DUCT TEMPERATURE,AFT CABIN (17HK) to ground.
(3) If the fault continues:
- do a check that the resistance of the AFT cabin-duct overheat sensor (20HK) measured between connector A/A and A/B is in these limits (Ref. ASM 21-63/03):
Temp (Deg.C) OHMS ---------------------------
+ 10 18820 +/- 5 %
+ 18 13340 +/- 5 %
+ 25 10000 +/- 5 %
+ 30 8197 +/- 5 %
+ 40 5598 +/- 5 %
+ 50 3903 +/- 5 %
(a) If the resistance values are out of the specified limits:
- replace the SENSOR-DUCT TEMPERATURE,AFT CABIN (20HK) (Ref. AMM TASK 21-63-18-000-001) and (Ref. AMM TASK 21-63-18-400-001).
(b) If the resistance values are in the specified limits:
- do a check and repair the wiring (Ref. ASM 21-63/03) from:
- the SENSOR-DUCT TEMPERATURE,AFT CABIN (20HK) to the ZC (8HK) and,
- the SENSOR-DUCT TEMPERATURE,AFT CABIN (20HK) to ground.
(4) If the fault continues:
- replace the VALVE-TRIM AIR,AFT CABIN (13HK) (Ref. AMM TASK 21-63-51-000-001) and (Ref. AMM TASK 21-63-51-400-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 051-052, ∞∞21-63-00∞∞∞∞∞∞∞∞∞∞Page 264
Aug 01/05R
CES
(5) If the fault continues:
- do a check and repair the wiring (Ref. ASM 21-63/03) from:
- the VALVE-TRIM AIR,AFT CABIN (13HK) to the ZC (8HK) and,
- the VALVE-TRIM AIR,AFT CABIN (13HK) to ground.
(6) If the fault continues:
- replace the VALVE-PRESSURE REGULATING (14HK) (Ref. AMM TASK 21-63-52-000-001) and (Ref. AMM TASK 21-63-52-400-001).
(7) If the fault continues:
- do a check and repair the wiring (Ref. ASM 21-63/03) from:
- the VALVE-PRESSURE REGULATING (14HK) to the ZC (8HK) and,
- the VALVE-PRESSURE REGULATING(14HK) to ground.
(8) If the fault continues:
- replace the CONT-ZONE TEMPERATURE (8HK) (Ref. AMM TASK 21-63-34-000-001) and (Ref. AMM TASK 21-63-34-400-001).
B. If the test gives the maintenance message TEST OK, but on the ECAM upper DU the warning COND AFT CAB DUCT OVHT comes on:
- do a check of the AFT cabin-duct inlet temperature on the ECAM COND page.
(1) If the temperature is below 70 Deg.C:
- replace the SENSOR-DUCT OVHT TEMPERATURE,AFT CABIN (20HK) (Ref. AMM TASK 21-63-18-000-001) and (Ref. AMM TASK 21-63-18-400-001).
C. Do the test as given in the Para. 3.A.
5. Close-up
________
A. Put the aircraft back to its initial configuration.
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
TASK 21-63-00-810-827
Zone Cont Electrical Component with Short Circuit (Primary/Secondary Channels)
1. Possible Causes
_______________
- CONT-ZONE TEMPERATURE (8HK)
- SENSOR-MIXER UNIT TEMPERATURE CABIN (25HK)
- TRIM VALVE CKPT (11HK)
- VALVE-TRIM AIR,FWD CABIN (12HK)
- VALVE-TRIM AIR,AFT CABIN (13HK)
- SENSOR-DUCT TEMPERATURE,COCKPIT (15HK)
- SENSOR-DUCT TEMPERATURE,FWD CABIN (16HK)
- SENSOR-DUCT TEMPERATURE,AFT CABIN (17HK)
- SENSOR-TEMPERATURE,COCKPIT (21HK)
- SENSOR-TEMPERATURE, FWD CABIN (22HK)
- SENSOR-TEMPERATURE, AFT CABIN (23HK)
- SENSOR-MIXER UNIT TEMPERATURE COCKPIT (24HK)
- SEL-TEMPERATURE, AIR COND/COCKPIT (27HK)
- SEL-TEMPERATURE, AIR COND/FWD CABIN (28HK)
- SEL-TEMPERATURE, AIR COND/AFT CABIN (29HK)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 21-63-00-710-004 Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU AMM 21-63-11-000-001 Removal of the Temperature Selector (27HK, 28HK, 29HK) AMM 21-63-11-400-001 Installation of the Temperature Selector (27HK,28HK,29HK) AMM 21-63-15-000-001 Removal of the Duct Temperature Sensors 15HK, 16HK and 17HK AMM 21-63-15-400-001 Installation of the Duct Temperature Sensors 15HK,