* GND and pins 15J and 15K.
(a) If there is no short circuit install the CONT-AIR COND SYSTEM 1 (47HH) (Ref. AMM TASK 21-61-34-400-002).
(b) If there is a short circuit at the connector (47HH/AB) disconnect the electrical connector (8HH/A) from the ACTUATOR-AIR INLET FLAP (8HH):
- do a check for a short circuit between,
* pins J and K and,
* GND and pins J and K.
- if there is a short circuit repair the related wiring between,
* connector (8HH/A) pin J and ACSC1 connector (47HH/AB) pin 15J,
* connector (8HH/A) pin K and ACSC1 connector (47HH/AB) pin 15K.
- if there is no short circuit in the wiring replace the ACTUATOR-AIR INLET FLAP (8HH),
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 282
201-299, 301-399, 401-499, Aug 01/05 CES (Ref. AMM TASK 21-61-51-000-001) and, (Ref. AMM TASK 21-61-51-400-001).
- install the CONT-AIR COND SYSTEM 1 (47HH) (Ref. AMM TASK 21-61-34-400-002).
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
C. If the fault continues:
(1) Swap the PC 1 (7HH) and the PC 2 (27HH)
(Ref. AMM TASK 21-61-34-000-001) and,
(Ref. AMM TASK 21-61-34-400-001).
(a) If the fault moves with the PC 1:
- swap back the PC 1 (7HH) and the PC 2 (27HH) (Ref. AMM TASK 21-61-34-000-001) and, (Ref. AMM TASK 21-61-34-400-001).
- replace the CONTROLLER-PACK 1 TEMP (7HH) (Ref. AMM TASK 21-61-34-000-001) and, (Ref. AMM TASK 21-61-34-400-001).
(2) If the fault does not move with the PC 1:
- swap back the PC 1 (7HH) and the PC 2 (27HH) (Ref. AMM TASK 21-61-34-000-001) and, (Ref. AMM TASK 21-61-34-400-001).
R **ON A/C 401-499,
C. If the fault continues:
(1) Swap the ACSC1 (47HH) and the ACSC2 (57HH)
(Ref. AMM TASK 21-61-34-000-002) and,
(Ref. AMM TASK 21-61-34-400-002).
(a) If the fault moves with the ACSC1:
- swap back the ACSC1 (47HH) and the ACSC2 (57HH) (Ref. AMM TASK 21-61-34-000-002) and, (Ref. AMM TASK 21-61-34-400-002).
- replace the CONT-AIR COND SYSTEM 1 (47HH) (Ref. AMM TASK 21-61-34-000-002) and, (Ref. AMM TASK 21-61-34-400-002).
(2) If the fault does not move with the ACSC1:
- swap back the ACSC1 (47HH) and the ACSC2 (57HH) (Ref. AMM TASK 21-61-34-000-002) and, (Ref. AMM TASK 21-61-34-400-002).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : ALL ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 283
Aug 01/05 CES
**ON A/C 001-003, 051-054,
D. If the fault continues:
(1) Disconnect the electrical connector (11HH/A) from the SENSOR-WATER EXTRACTOR TEMPERATURE (11HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (11HH/A) do a check for voltage between,
* pins E and F.
(a) If the voltage is between 4.8VDC and 5.2VDC:
- replace the SENSOR-WATER EXTRACTOR TEMPERATURE (11HH) (Ref. AMM TASK 21-61-13-000-001) and, (Ref. AMM TASK 21-61-13-400-001).
(b) If the voltage is not between 4.8VDC and 5.2VDC:
- disconnect the electrical connector (8HH/A) from the ACTUATOR-AIR INLET FLAP (8HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (11HH/A) do a check for voltage again.
1_ If the voltage is between 4.8VDC and 5.2VDC:
- replace the ACTUATOR-AIR INLET FLAP (8HH)
(Ref. AMM TASK 21-61-51-000-001) and,
(Ref. AMM TASK 21-61-51-400-001).
- connect the electrical connector (11HH/A).
2_ If the voltage is not between 4.8VDC and 5.2VDC:
- connect the electrical connector (8HH/A),
- repeat para. 4.D.(1).(b) for,
* connector (9HH/A) and the ACTUATOR-AIR OUTLET FLAP (9HH)
(Ref. AMM TASK 21-61-52-000-001) and
(Ref. AMM TASK 21-61-52-400-001),
* connector (10HH/A) and the VALVE-TURBINE BYPASS (10HH)
(Ref. AMM TASK 21-61-53-000-001) and,
(Ref. AMM TASK 21-61-53-400-001),
* connector (12HH/A) and the SENSOR-COMPRESSOR TEMPERATURE
(12HH)
(Ref. AMM TASK 21-61-11-000-001) and,