「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-51-00∞∞∞∞∞∞∞∞∞∞Page 255
201-299, 301-399, 401-499, Aug 01/05 CES (3) On the ECAM BLEED page:
- make sure that the pack 1 inlet pressure indication shows a minimum of 24 PSI.
NOTE : If the indication shows less than 24 PSI you must:
____
- increase the ground pressure supply until the indication shows a minimum of 24 PSI.
B. Start the engines (Ref. AMM TASK 71-00-00-710-003) if necessary.
4. Fault Isolation
_______________
R **ON A/C 004-049, 055-099, 101-149, 151-199, 201-299, 301-399,
A. When the pack flow selector is at the LO or NORM position:
- on the upper ECAM DU if the pack 2 flow shows in the HI flow position and both pack flow-control valve indications show green,
- replace the VALVE-FLOW CTL (8HB) (Ref. AMM TASK 21-51-51-000-001) and (Ref. AMM TASK 21-51-51-400-001).
R **ON A/C 401-499,
A. When the pack flow selector is at the LO or NORM position:
- on the upper ECAM DU if the pack 2 flow shows in the HI flow position and both pack flow-control valve indications show green,
- replace the FLOW CONTROL SYSTEM (24HB) (Ref. AMM TASK 21-51-51-000-001) and (Ref. AMM TASK 21-51-51-400-001).
**ON A/C 004-049, 055-099, 101-105, 151-199, 201-299, 301-302,
B. This procedure is only applicable for the Flow Control Valves P/N 1303 series.
(1) When the pack flow selector is at the LO or NORM position:
- on the upper ECAM DU if the pack 2 flow shows in the HI flow position and both pack flow-control valve indications show green,
(a) do a check of the wiring (Ref. ASM 21-51/01) and (Ref. ASM 21-51/01) from:
- the FCV (8HB/A) pin C to the PACK1 TEMP CONTROLLER (7HH/AA) pin 7B.
(b) If the fault continues:
- replace the P2 FLOW CTL VALVE (8HB) (Ref. AMM TASK 21-51-51-000-001) and (Ref. AMM TASK 21-51-51-400-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-51-00∞∞∞∞∞∞∞∞∞∞Page 256
201-299, 301-399, 401-499, Aug 01/05 CES
R **ON A/C 004-049, 055-099, 101-149, 151-199, 201-299, 301-399, 401-499,
5. Close-up
________
**ON A/C 004-049, 055-099, 101-105, 151-199, 201-299, 301-302,
A. This procedure is only necessary after you do the work step Para. 4. B. (a).
- Do the procedures given in para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-51-00∞∞∞∞∞∞∞∞∞∞Page 257
201-299, 301-399, 401-499, Aug 01/05 CES
R **ON A/C 401-499,
TASK 21-51-00-810-817
Pack 1 Flow Sensor / Inlet Pressure Sensor Fault
1. Possible Causes_______________
- SENSOR-DELTA P, PACK 1 (23HB2)
- SENSOR-PRESS, PACK 1 INLET (23HB1)
- CONT-AIR COND SYSTEM 1 (47HH)
- wiring
2. Job Set-up Information______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 21-51-11-000-001 Removal of the Differential Pressure Sensor 9HB (10HB)
AMM 21-51-11-400-001 Installation of the Differential Pressure Sensor 9HB (10HB)
AMM 21-61-00-710-001 Operational Test of the Pack Temperature-Control System
AMM 21-61-16-000-001 Removal of the Pack-Inlet Pressure Sensor 16HH (36HH)
AMM 21-61-16-400-002 Installation of the Pack-Inlet Pressure Sensor 16HH (36HH)
AMM 21-61-34-000-002 Removal of the Air-Conditioning System Controller (47HH, 57HH)
AMM 21-61-34-400-002 Installation of the Air-Conditioning System Controller (47HH, 57HH)
ASM 21-61/01
3. Fault Confirmation__________________
A. Do the operational test of the pack temperature-control system (Ref. AMM TASK 21-61-00-710-001).
NOTE : If a fault is detected, the ACSC1 gives a fault code for shop
____ maintenance in addition to the related CFDS message(s) (refer to TSM chapter 21-63-00, page block 301).
4. Fault Isolation
_______________
A. If the test gives the maintenance message P1 FLOW SENSOR(23HB2)/PIPS(23HB1): 中国航空网 www.aero.cn 航空翻译 www.aviation.cn 本文链接地址:A320 Trouble Shooting Manual 排故手册 AIR CONDITIONING 空调2(7)