AMM  21-61-00-710-001 
AMM  21-61-11-000-001 
AMM  21-61-11-400-001 
AMM  21-61-12-000-001 
AMM  21-61-12-400-001 
AMM  21-61-15-000-001 
AMM  21-61-15-400-001 
AMM  21-61-34-000-001 
AMM  21-61-34-000-002 
AMM  21-61-34-400-001 
AMM  21-61-34-400-002 
AMM  21-61-41-000-001 
AMM  21-61-41-400-001 
AMM  32-42-34-400-001 
ASM  21-61/01
 ASM  21-61/02
 ASM  21-61/02

 3. Fault Confirmation
__________________
Operational Test of the Pack Temperature-Control SystemRemoval of the Compressor Outlet - Temperature Sensor 12HH (32HH)Installation of the Compressor Outlet - Temperature Sensor 12HH (32HH)Removal of the Compressor Overheat - Temperature Sensor 15HH (35HH)Installation of the Compressor Overheat - Temperature Sensor 15HH (35HH)Removal of the Pack Outlet - Temperature Sensors 13HH and 34HHInstallation of the Pack Outlet - Temperature Sensors 13HH and 34HHRemoval of the Pack Controller (7HH, 27HH)Removal of the Air-Conditioning System Controller (47HH, 57HH)Installation of the Pack Controller (7HH, 27HH)Installation of the Air-Conditioning System Controller (47HH, 57HH)Removal of the Anti-Ice Valve 17HH (37HH)Installation of the Anti-Ice Valve 17HH (37HH)Installation of the Braking/Steering Control Unit (BSCU) (10GG)
 A. APU Bleed-Air Pressure Check
 (1) Do the pre-conditioning with the APU (Ref. AMM TASK 12-33-21-618-001).

 (2) Make sure that the APU bleed-air pressure is higher than 12 psi (0.8273 bar).

 (3) Stop the pre-conditioning with the APU (Ref. AMM TASK 12-33-21-618-001).


 (4) If the APU bleed-air pressure is lower than or equal to 12 psi R (0.8273 bar), do the trouble shooting of the APU (refer to the fault R symptom list / 49-OBSV, APU BLEED FAULT No, Low or Fluctuating APU R Bleed-Air Pressure) before you continue with the subsequent R procedure.
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 211
 May 01/05 CES


R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,

 B. Test
 (1) Do the operational test of the pack temperature-control system (Ref. AMM TASK 21-61-00-710-001).
 NOTE : If a fault is detected, the PC gives a fault code for shop
____ maintenance in addition to the related CFDS message(s) (refer to TSM chapter 21-63-00, page block 301).
 (2) Do the pre-conditioning through the HP ground connection (Ref. AMM TASK 12-33-21-618-001).

 (3) Do a check that the pack 2 inlet-pressure indication on the ECAM BLEED page is > 20 PSI.

 (4) Do a check of the pack 2 flow indicator, the compressor discharge and pack outlet temperature on the ECAM BLEED page.


 (5) Do a check to see that there is airflow at the pack 2 ram-air outlet. R **ON A/C 401-499,
 B. Test
 (1) Do the operational test of the pack temperature-control system (Ref. AMM TASK 21-61-00-710-001).

 (2) Do the pre-conditioning through the HP ground connection (Ref. AMM TASK 12-33-21-618-001).

 (3) Do a check that the pack 2 inlet-pressure indication on the ECAM BLEED page is > 20 PSI.

 (4) Do a check of the pack 2 flow indicator, the compressor discharge and pack outlet temperature on the ECAM BLEED page.


 (5) Do a check to see that there is airflow at the pack 2 ram-air outlet. **ON A/C ALL
 4. Fault Isolation
_______________
 A. If the pack 2 inlet-pressure indication on the ECAM BLEED page is < 20 PSI:
 - increase the pressure to > 25 PSI.
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 212
 Aug 01/05 CES


R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
 B. For a Compressor Discharge Overheat Condition:
 (1) If you select on the panel 30VU low airflow and the pack 2 flow indicator on the ECAM BLEED page moves to the HI indication:

 - replace the VALVE-FLOW CTL (8HB) (Ref. AMM TASK 21-51-51-000-001) and (Ref. AMM TASK 21-51-51-400-001).

 (2) If the fault continues:


 - do a check that the resistance of the compressor temperature sensor (32HH) measured between connector A/A and A/B is in these limits (Ref. ASM 21-61/02):
 Temp (Deg.C) OHMS ---------------------------
+ 10 103.9 +/- 0.5

 + 20 107.8 +/- 0.5
 
中国航空网 www.aero.cn
航空翻译 www.aviation.cn
本文链接地址:A320 Trouble Shooting Manual 排故手册 AIR CONDITIONING 空调2(17)