(2) If the fault continues:
- do a check that the resistance of the compressor overheat sensor (35HH) measured between connector A/A and A/B is in these limits (Ref. ASM 21-61/02):
Temp (Deg.C) OHMS ---------------------------
+ 10 103.9 +/- 0.5
+ 20 107.8 +/- 0.5
+ 30 111.7 +/- 0.5
+ 50 119.4 +/- 0.5
+ 70 127.1 +/- 0.5
+ 100 138.5 +/- 0.5
(3) If the resistance values are out of the specified limits:
- replace the SENSOR-COMPRESSOR OVERHEAT (35HH) (Ref. AMM TASK 21-61-12-000-001) and (Ref. AMM TASK 21-61-12-400-001).
(4) If the fault continues:
(a) Swap the SDACIs (1WV1 and 1WV2). (Ref.AMM Task 31-55-34-401)
(b) If this action has solved the problem:
- replace the SDAC which formerly was SDAC#1.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 001-003, 051-054, 401-499, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 231
Aug 01/05 CES
(5) If the fault continues:
(a) Open the CBIs for the Pack Controller #1 + #2.
(b) Disconnect the Pack ControllerIs. (Ref.AMM Task 21-61-34-401)
(c) Disconnect the electrical connectors at the FCV#1(11HB) and FCV#2(8HB).
- (Ref.AMM Task 21-51-51-401).
(d) Disconnect the SDAC#1.
(e) Do a check for GND at the SDAC#1 connector AA pin 10D.
(f) Do a check for GND at the SDAC#1 connector AA pin 13B.
NOTE : there should be no GND contact
____
(g) If there is no GND contact, reconnect the SDAC#1.
(h) If there is GND contact, do a check of the wiring and repair if nessesary.
R **ON A/C 004-049, 055-099, 101-149, 151-199, 201-299, 301-399,
C. If the test confirms the fault:
- do a check that the resistance of the compressor temperature sensor (32HH) measured between connector A/A and A/B is in these limits (Ref. ASM 21-61/02):
Temp (Deg.C) OHMS ---------------------------
+ 10 103.9 +/- 0.5
+ 20 107.8 +/- 0.5
+ 30 111.7 +/- 0.5
+ 50 119.4 +/- 0.5
+ 70 127.1 +/- 0.5
+ 100 138.5 +/- 0.5
(1) If the resistance values are out of the specified limits:
- replace the SENSOR-COMPRESSOR TEMPERATURE (32HH) (Ref. AMM TASK 21-61-11-000-001) and (Ref. AMM TASK 21-61-11-400-001).
(2) If the fault continues:
- do a check that the resistance of the compressor overheat sensor (35HH) measured between connector A/A and A/B is in these limits (Ref. ASM 21-61/02):
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 001-049, 051-099, 101-149, 151-199, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 232
201-299, 301-399, Aug 01/05 CES
Temp (Deg.C) OHMS
---------------------------
+ 10 103.9 +/- 0.5
+ 20 107.8 +/- 0.5
+ 30 111.7 +/- 0.5
+ 50 119.4 +/- 0.5
+ 70 127.1 +/- 0.5
+ 100 138.5 +/- 0.5
(a) If the resistance values are out of the specified limits:
- replace the SENSOR-COMPRESSOR OVERHEAT (35HH) (Ref. AMM TASK 21-61-12-000-001) and (Ref. AMM TASK 21-61-12-400-001).
(3) If the fault continues: Do the inspection of the delta P sense lines (Ref. AMM TASK 21-51-00-200-001)
(4) If the fault continues: Replace the SENSOR-PRESSURE (9HB) (Ref. AMM TASK 21-51-11-000-001) and (Ref. AMM TASK 21-51-11-400-001).
(5) If the fault continues:
(a) Swap the SDACIs (1WV1 and 1WV2). (Ref.AMM Task 31-55-34-401)
(b) If this action has solved the problem:
- replace the SDAC which formerly was SDAC#1.
(6) If the fault continues:
(a) Open the CBIs for the Pack Controller #1 + #2.
(b) Disconnect the Pack ControllerIs. (Ref.AMM Task 21-61-34-401)
(c) Disconnect the electrical connectors at the FCV#1(11HB) and FCV#2(8HB).
- (Ref.AMM Task 21-51-51-401).
(d) Disconnect the SDAC#1.
(e) Do a check for GND at the SDAC#1 connector AA pin 10D.
(f) Do a check for GND at the SDAC#1 connector AA pin 13B. NOTE : there should be no GND contact
____
(g) If there is no GND contact, reconnect the SDAC#1.
(h) If there is GND contact, do a check of the wiring and repair if nessesary.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 233