R **ON A/C 004-049, 055-099, 101-149, 151-199, 201-299, 301-399,
D. If the fault continues:
(1) Disconnect the electrical connector (11HH/A) from the SENSOR-WATER EXTRACTOR TEMPERATURE (11HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (11HH/A) do a check for voltage between,
* pins E and F.
(a) If the voltage is between 9.6VDC and 10.4VDC:
- replace the SENSOR-WATER EXTRACTOR TEMPERATURE (11HH) (Ref. AMM TASK 21-61-13-000-001) and, (Ref. AMM TASK 21-61-13-400-001).
(b) If the voltage is not between 9.6VDC and 10.4VDC:
- disconnect the electrical connector (8HH/A) from the ACTUATOR-AIR INLET FLAP (8HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (11HH/A) do a check for voltage again.
1_ If the voltage is between 9.6VDC and 10.4VDC:
- replace the ACTUATOR-AIR INLET FLAP (8HH)
(Ref. AMM TASK 21-61-51-000-001) and,
(Ref. AMM TASK 21-61-51-400-001).
- connect the electrical connector (11HH/A).
2_ If the voltage is not between 9.6VDC and 10.4VDC:
- connect the electrical connector (8HH/A),
- repeat para. 4.D.(1).(b) for,
* connector (10HH/A) and the VALVE-TURBINE BYPASS (10HH)
(Ref. AMM TASK 21-61-53-000-001) and,
(Ref. AMM TASK 21-61-53-400-001),
* connector (12HH/A) and the SENSOR-COMPRESSOR TEMPERATURE
(12HH)
(Ref. AMM TASK 21-61-11-000-001) and,
(Ref. AMM TASK 21-61-11-400-001),
* connector (11HB/A) and the VALVE-FLOW CTL (11HB)
(Ref. AMM TASK 21-51-51-000-001) and,
(Ref. AMM TASK 21-51-51-400-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 285
201-299, 301-399, Aug 01/05 CES
R **ON A/C 401-499,
D. If the fault continues:
(1) Disconnect the electrical connector (11HH/A) from the SENSOR-WATER EXTRACTOR TEMPERATURE (11HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (11HH/A) do a check for voltage between,
* pins E and F.
(a) If the voltage is between 9.6VDC and 10.4VDC:
- replace the SENSOR-WATER EXTRACTOR TEMPERATURE (11HH) (Ref. AMM TASK 21-61-13-000-001) and, (Ref. AMM TASK 21-61-13-400-001).
(b) If the voltage is not between 9.6VDC and 10.4VDC:
- disconnect the electrical connector (8HH/A) from the ACTUATOR-AIR INLET FLAP (8HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (11HH/A) do a check for voltage again.
1_ If the voltage is between 9.6VDC and 10.4VDC:
- replace the ACTUATOR-AIR INLET FLAP (8HH)
(Ref. AMM TASK 21-61-51-000-001) and,
(Ref. AMM TASK 21-61-51-400-001).
- connect the electrical connector (11HH/A).
2_ If the voltage is not between 9.6VDC and 10.4VDC:
- connect the electrical connector (8HH/A),
- repeat para. 4.D.(1).(b) for,
* connector (10HH/A) and the VALVE-TURBINE BYPASS (10HH)
(Ref. AMM TASK 21-61-53-000-001) and,
(Ref. AMM TASK 21-61-53-400-001),
* connector (12HH/A) and the SENSOR-COMPRESSOR TEMPERATURE
(12HH)
(Ref. AMM TASK 21-61-11-000-001) and,
(Ref. AMM TASK 21-61-11-400-001),
* connector (23HB/A) and the FLOW CTL UNIT - PACK 1 (23HB)
(Ref. AMM TASK 21-51-51-000-001) and,
(Ref. AMM TASK 21-51-51-400-001).
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
E. If the fault continues:
(1) disconnect the electrical connector (7559VC/A) from the SENSOR-PACK INLET PRESSURE (16HH).
- make sure that the electrical connector is clean and in the correct condition.
- at the electrical connector (7559VC) do a check for 15VDC from pack controller primary channel between,
* pins A and C (+15VDC) and,
* D and C (-15VDC).
(a) If the voltage is correct:
- replace the SENSOR-PACK INLET PRESSURE (16HH) (Ref. AMM TASK 21-61-16-000-001) and, (Ref. AMM TASK 21-61-16-400-002).
中国航空网 www.aero.cn
航空翻译 www.aviation.cn
本文链接地址:A320 Trouble Shooting Manual 排故手册 AIR CONDITIONING 空调2(42)