AMM 21-51-13-000-001 Removal of the Pack-Inlet Pressure Sensor 23HB1
 (24HB1) AMM 21-51-13-400-002 AMM 21-51-51-000-001 Removal of the Pack Flow-Control Valve AMM 21-51-51-400-001 Installation of the Pack Flow-Control Valve AMM 21-61-00-710-001 Operational Test of the Pack Temperature-Control
 System AMM 21-61-11-000-001 Removal of the Compressor Outlet - Temperature Sensor 12HH (32HH) AMM 21-61-11-400-001 Installation of the Compressor Outlet - Temperature Sensor 12HH (32HH) AMM 21-61-13-000-001 Removal of the Water-Extractor Temperature Sensors 11HH and 31HH AMM 21-61-13-400-001 Installation of the Water-Extractor Temperature
 Sensors 11HH and 31HH AMM 21-61-16-000-001 Removal of the Pack-Inlet Pressure Sensor 16HH (36HH) AMM 21-61-16-400-002 Installation of the Pack-Inlet Pressure Sensor 16HH
 (36HH) AMM 21-61-34-000-001 Removal of the Pack Controller (7HH, 27HH) AMM 21-61-34-000-002 Removal of the Air-Conditioning System Controller
 (47HH, 57HH)
 AMM 21-61-34-400-001 Installation of the Pack Controller (7HH, 27HH)

 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page 294
 Aug 01/05R CES


 -------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 21-61-34-400-002 Installation of the Air-Conditioning System
 Controller (47HH, 57HH) AMM 21-61-51-000-001 Removal of the Air-Inlet Flap Actuator 8HH and 28HH AMM 21-61-51-400-001 Installation of the Air-Inlet Flap Actuator 8HH and
 28HH AMM 21-61-52-000-001 Removal of the Air-Outlet Flap Actuator 9HH (29HH) AMM 21-61-52-400-001 Installation of the Air-Outlet Flap Actuator 9HH
 (29HH)
 AMM 21-61-53-000-001 Removal of the Bypass Valve 10HH (30HH)
 AMM 21-61-53-400-001 Installation of the Bypass Valve 10HH (30HH)
 ASM 21-51/01
 ASM 21-61/01
 ASM 21-61/02
 ASM 21-61/04
 AWM 21-61-06
 AWM 21-61-07
 AWM 21-61-08
 AWM 21-61-09

 3. Fault Confirmation
__________________
 **ON A/C 001-049, 051-061, 101-102, 201-202,
 A. Warning Confirmation
 NOTE : This Para. and the Paras. B, C and D which follow are work steps
____ necessary to confirm the nature (spurious or actual) of the ECAM warning AIR PACK2 REGUL FAULT.
 (1) On the panel 130VU push the MASTER CAUT pushbutton switch.
 B. Open this(these) circuit breaker(s):
 -------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------122VU AIR COND/PACK TEMP/CTL SYS1/2/115VAC 21HH W22 122VU AIR COND/PACK TEMP CTL SYS2/2/115VAC 22HH Y20
 C. Close this(these) circuit breaker(s):

 -------------------------------------------------------------------------------PANEL DESIGNATION IDENT. LOCATION -------------------------------------------------------------------------------122VU AIR COND/PACK TEMP/CTL SYS1/2/115VAC 21HH W22 122VU AIR COND/PACK TEMP CTL SYS2/2/115VAC 22HH Y20
 Aug 01/05R CES


 D. Wait for a minimum of 60 seconds.

R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
 E. Test
 (1) Do a read out of the post flight report and do the operational test of the pack-temperature control system (Ref. AMM TASK 21-61-00-710-001).
 NOTE : If the test finds a fault the PC gives a fault code for shop
____ maintenance and also the related CFDS message(s) (refer to chapter 21-63-00 page block 301).
R **ON A/C 401-499,
 E. Test
 (1) Do a read out of the post flight report and do the operational test of the pack-temperature control system (Ref. AMM TASK 21-61-00-710-001).
 **ON A/C ALL
 4. Fault Isolation
_______________
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
 A. * If the post flight report gives the warning AIR PACK 2 REGUL FAULT without a maintenance message and,
 * no AIR PACK 2 REGUL FAULT shows on the ECAM upper DU and,
 - no further action is necessary. ** If the post flight report gives the warning AIR PACK 2 REGUL FAULT and, ** the ECAM upper DU gives the warning AIR PACK 2 REGUL FAULT or, *** If the post flight report gives the warning AIR PACK 2 REGUL FAULT with, *** the maintenance message NO DATA FROM P2 CONT and, *** the operational test of the pack-temperature control system gives the maintenance message NO TEST RECEPTION FROM P2 CONT:

 - do the work steps which follow.


 NOTE : Additional Information
 