R **ON A/C 004-049, 055-099, 101-149, 151-199, 201-299, 301-399,
D. If the fault continues:
(1) Disconnect the electrical connector (31HH/A) from the SENSOR-WATER EXTRACTOR TEMPERATURE (31HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (31HH/A) do a check for voltage between,
* pins E and F.
(a) If the voltage is between 9.6VDC and 10.4VDC:
- replace the SENSOR-WATER EXTRACTOR TEMPERATURE (31HH) (Ref. AMM TASK 21-61-13-000-001) and, (Ref. AMM TASK 21-61-13-400-001).
(b) If the voltage is not between 9.6VDC and 10.4VDC:
- disconnect the electrical connector (28HH/A) from the ACTUATOR-AIR INLET FLAP (28HH),
- make sure that the electrical connector is clean and in the correct condition.
- at the electrical connector (31HH/A) do a check for voltage again.
1_ If the voltage is between 9.4VDC and 10.4VDC:
- replace the ACTUATOR-AIR INLET FLAP (28HH)
(Ref. AMM TASK 21-61-51-000-001) and,
(Ref. AMM TASK 21-61-51-400-001).
- connect the electrical connector (31HH/A).
2_ If the voltage is not between 9.6VDC and 10.4VDC:
- connect the electrical connector (28HHA) (Ref. AMM TASK 21-
61-51-400-001).
- repeat para. 4.D.(1).(b) for:
* connector (30HH/A) and the VALVE-TURBINE BYPASS (30HH)
(Ref. AMM TASK 21-61-53-000-001) and,
(Ref. AMM TASK 21-61-53-400-001),
* connector (32HH/A) and the SENSOR-COMPRESSOR TEMPERATURE
(32HH)
(Ref. AMM TASK 21-61-11-000-001) and,
(Ref. AMM TASK 21-61-11-400-001),
* connector (8HB/A) and the VALVE-FLOW CTL (8HB)
(Ref. AMM TASK 21-51-51-000-001) and,
(Ref. AMM TASK 21-51-51-400-001).
- connect the electrical connector (31HH/A).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 004-049, 055-099, 101-149, 151-199, ∞∞21-61-00∞∞∞∞∞∞∞∞∞∞Page A202
201-299, 301-399, Aug 01/05 CES
R **ON A/C 401-499,
D. If the fault continues:
(1) Disconnect the electrical connector (31HH/A) from the SENSOR-WATER EXTRACTOR TEMPERATURE (31HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (31HH/A) do a check for voltage between,
* pins E and F.
(a) If the voltage is between 9.6VDC and 10.4VDC:
- replace the SENSOR-WATER EXTRACTOR TEMPERATURE (31HH) (Ref. AMM TASK 21-61-13-000-001) and, (Ref. AMM TASK 21-61-13-400-001).
(b) If the voltage is not between 9.6VDC and 10.4VDC:
- disconnect the electrical connector (28HH/A) from the P2 RAM AIR IN ACTUATOR (28HH),
- make sure that the electrical connector is clean and in the correct condition,
- at the electrical connector (31HH/A) do a check for voltage again.
1_ If the voltage is between 9.6VDC and 10.4VDC:
- replace the P2 RAM AIR IN ACTUATOR (28HH)
(Ref. AMM TASK 21-61-51-000-001) and,
(Ref. AMM TASK 21-61-51-400-001).
- connect the electrical connector (31HH/A).
2_ If the voltage is not between 9.6VDC and 10.4VDC:
- connect the electrical connector (28HH/A),
- repeat para. 4.D.(1).(b) for,
* connector (30HH/A) and the VALVE-TURBINE BYPASS (30HH)
(Ref. AMM TASK 21-61-53-000-001) and,
(Ref. AMM TASK 21-61-53-400-001),
* connector (32HH/A) and the SENSOR-COMPRESSOR TEMPERATURE
(32HH)
(Ref. AMM TASK 21-61-11-000-001) and,