 B. If the test gives the maintenance message TEST OK, but on the ECAM upper DU the warning COND CKPT DUCT OVHT comes on:
 - do a check of the cockpit inlet temperature on the ECAM COND page.
 (1) If the temperature is below 70 Deg.C:
 - replace the SENSOR-DUCT OVHT TEMPERATURE,COCKPIT (18HK) (Ref. AMM TASK 21-63-18-000-001) and (Ref. AMM TASK 21-63-18-400-001).
 C. Do the test as given in the Para. 3.A.
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 051-052, ∞∞21-63-00∞∞∞∞∞∞∞∞∞∞Page 258
 Aug 01/05R CES


R **ON A/C 051-052, 106-149, 303-399,
 5. Close-up
________ R **ON A/C 051-052,
 A. Put the aircraft back to its initial configuration.

 TASK 21-63-00-810-824


 FWD Cabin Duct Overheat Detection
 1. Possible Causes
_______________
 - SENSOR-DUCT TEMPERATURE,FWD CABIN (16HK)

 - SENSOR-DUCT OVHT TEMPERATURE,FWD CABIN (19HK)

 - VALVE-TRIM AIR,FWD CABIN (12HK)

 - VALVE-PRESSURE REGULATING (14HK)

 - CONT-ZONE TEMPERATURE (8HK)

 - wiring


 2. Job Set-up Information
______________________
 A. Referenced Information
 -------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 21-63-00-710-004 Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU AMM 21-63-15-000-001 Removal of the Duct Temperature Sensors 15HK, 16HK and 17HK AMM 21-63-15-400-001 Installation of the Duct Temperature Sensors 15HK, 16HK and 17HK AMM 21-63-18-000-001 Removal of the Duct Overheat-Temperature Sensors 18HK, 19HK and 20HK AMM 21-63-18-400-001 Installation of the Duct Overheat-Temperature Sensors
 18HK, 19HK and 20HK AMM 21-63-34-000-001 Removal of the Zone Controller (8HK) AMM 21-63-34-400-001 Installation of the Zone Controller (8HK) AMM 21-63-51-000-001 Removal of the Trim Air Valve (11HK,12HK,13HK) AMM 21-63-51-400-001 Installation of the Trim Air Valve (11HK,12HK,13HK) AMM 21-63-52-000-001 Removal of the Pressure Regulating Valve 14HK AMM 21-63-52-400-001 Installation of the Pressure Regulating Valve 14HK ASM 21-63/02 ASM 21-63/03 ASM 21-63/03
 3. Fault Confirmation
__________________
 A. Do the operational test of the cockpit and cabin temperature-control system with CFDS/MCDU (Ref. AMM TASK 21-63-00-710-004).
 NOTE : If a fault is detected, the ZC gives a fault code for shop
____ maintenance in addition to the related CFDS message(s). For detailed information see the applicable Page Block 301.
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 051-052, ∞∞21-63-00∞∞∞∞∞∞∞∞∞∞Page 260
 Aug 01/05R
 CES

 4. Fault Isolation
_______________

 A. If the test confirms the fault:
 - do a check that the resistance of the FWD cabin-duct temperature sensor (16HK) measured between connector A/E and A/F and connector A/C and A/D is in these limits (Ref. ASM 21-63/03):
 Temp (Deg.C) OHMS ---------------------------
+ 10 18820 +/- 5 %

 + 18 13340 +/- 5 %

 + 25 10000 +/- 5 %

 + 30 8197 +/- 5 %

 + 40 5598 +/- 5 %

 + 50 3903 +/- 5 %


 (1) If the resistance values are out of the specified limits:

 - replace the SENSOR-DUCT TEMPERATURE,FWD CABIN (16HK) (Ref. AMM TASK 21-63-15-000-001) and (Ref. AMM TASK 21-63-15-400-001).

 (2) If the resistance values are in the specified limits:

 - do a check and repair the wiring (Ref. ASM 21-63/03) from:

 - the SENSOR-DUCT TEMPERATURE,FWD CABIN (16HK) to the ZC (8HK) and,

 - the SENSOR-DUCT TEMPERATURE,FWD CABIN (16HK) to ground.

 

 (3) If the fault continues:


 - do a check that the resistance of the FWD cabin-duct overheat sensor (19HK) measured between connector A/A and A/B is in these limits (Ref. ASM 21-63/03):
 Temp (Deg.C) OHMS ---------------------------
+ 10 18820 +/- 5 %

 + 18 13340 +/- 5 %

 + 25 10000 +/- 5 %

 + 30 8197 +/- 5 %

 + 40 5598 +/- 5 %

 + 50 3903 +/- 5 %


 (a) If the resistance values are out of the specified limits:

 - replace the SENSOR-DUCT OVHT TEMPERATURE,FWD CABIN (19HK) (Ref. AMM TASK 21-63-18-000-001) and (Ref. AMM TASK 21-63-18-400-001).

 (b) If the resistance values are in the specified limits:

 - do a check and repair the wiring (Ref. ASM 21-63/03) from:
 