R 1EFF : 401-499, 1 21-52-32Page 427 1 1 Aug 01/05 1 1 1CES 1
R  (15) TORQUE the nuts (5) to between 0.85 and 1.0 m.daN (75.22 and 88.49  
R  lbf.in) and wipe clean the excess COMMON GREASE (Material No. 04-012)  
R  from the retaining cables (7).  
R  NOTE : Hold the hexagon part of the retaining cables (7) to prevent____  
R  twisting of the cables when you torque the nuts (5).  
R  Make sure that there is no tension in the cables (7).  
R  This will give a safe and flexible connection.  
R  (16) Put the sleeve (20) in position on the condensor (19) and install the  
R  clamp (21).  
R  (17) Make sure that the clamp (21) is in the correct position.  
R  (18) TORQUE the clamp (21) to 0.28 m.daN (24.77 lbf.in).  
R  (19) Remove the blanking caps and connect the electrical connector (24).  
R  (20) Make sure that the work area is clean and clear of tool(s) and other 
 items.  
R  **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399, 
 Subtask 21-52-32-865-052 
 D. Remove the safety clip(s) and the tag(s) and close this(these) circuit 
 breaker(s):  
R  (1) FOR 10HM2 
 - 1HH, 2HH, 3HH, 4HH,  
R  (2) FOR 11HM2 
 - 21HH, 22HH, 23HH, 24HH.  
R  **ON A/C 401-499, 
 Subtask 21-52-32-865-052-A 
 D. Remove the safety clip(s) and the tag(s) and close this(these) circuit 
 breaker(s):  
R  (1) FOR 10HM2 
 - 49HH, 50HH, 51HH, 52HH,
R (2) FOR 11HM2
 -53HH, 54HH, 55HH, 56HH.
 **ON A/C ALL
 Subtask 21-52-32-710-050
 E. Test
 (1)
 Do the pre-conditioning through the HP ground connector (Ref. TASK 12-33-21-618-001) or with the APU (Ref. TASK 12-33-21-618-001).
 (2)
 Do a leak check of the condenser connections. NOTE : Minimum leakage is permitted. After the pack operates some
____ minutes, the leakage of air will reduce because the seals have their correct operating temperature.
 (3)
 Do a leak check of the sense line connections.
 NOTE : Leaks are not permitted.
____
 (4)
 After approx. 15 minutes stop the pre-conditioning (Ref. TASK 12-33-21-618-001) or (Ref. TASK 12-33-21-618-001).
 (5)
 Do the operational test of the cockpit and cabin temperature control (Ref. TASK 21-63-00-710-004).
 5. Close-up
________
 Subtask 21-52-32-410-051-A
 A. Close Access
 (1)
 Make sure that the work area is clean and clear of tool(s) and other items.
 (2)
 Install the access panel/s (Ref. TASK 53-35-13-400-002).
 (a)
 FOR 10HM2
 -191KB
 -191BB,
 (b)
 FOR 11HM2
 