R 1EFF : 401-499, 1 21-52-32Page 427 1 1 Aug 01/05 1 1 1CES 1
R (15) TORQUE the nuts (5) to between 0.85 and 1.0 m.daN (75.22 and 88.49
R lbf.in) and wipe clean the excess COMMON GREASE (Material No. 04-012)
R from the retaining cables (7).
R NOTE : Hold the hexagon part of the retaining cables (7) to prevent____
R twisting of the cables when you torque the nuts (5).
R Make sure that there is no tension in the cables (7).
R This will give a safe and flexible connection.
R (16) Put the sleeve (20) in position on the condensor (19) and install the
R clamp (21).
R (17) Make sure that the clamp (21) is in the correct position.
R (18) TORQUE the clamp (21) to 0.28 m.daN (24.77 lbf.in).
R (19) Remove the blanking caps and connect the electrical connector (24).
R (20) Make sure that the work area is clean and clear of tool(s) and other
items.
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
Subtask 21-52-32-865-052
D. Remove the safety clip(s) and the tag(s) and close this(these) circuit
breaker(s):
R (1) FOR 10HM2
- 1HH, 2HH, 3HH, 4HH,
R (2) FOR 11HM2
- 21HH, 22HH, 23HH, 24HH.
R **ON A/C 401-499,
Subtask 21-52-32-865-052-A
D. Remove the safety clip(s) and the tag(s) and close this(these) circuit
breaker(s):
R (1) FOR 10HM2
- 49HH, 50HH, 51HH, 52HH,
R (2) FOR 11HM2
-53HH, 54HH, 55HH, 56HH.
**ON A/C ALL
Subtask 21-52-32-710-050
E. Test
(1)
Do the pre-conditioning through the HP ground connector (Ref. TASK 12-33-21-618-001) or with the APU (Ref. TASK 12-33-21-618-001).
(2)
Do a leak check of the condenser connections. NOTE : Minimum leakage is permitted. After the pack operates some
____ minutes, the leakage of air will reduce because the seals have their correct operating temperature.
(3)
Do a leak check of the sense line connections.
NOTE : Leaks are not permitted.
____
(4)
After approx. 15 minutes stop the pre-conditioning (Ref. TASK 12-33-21-618-001) or (Ref. TASK 12-33-21-618-001).
(5)
Do the operational test of the cockpit and cabin temperature control (Ref. TASK 21-63-00-710-004).
5. Close-up
________
Subtask 21-52-32-410-051-A
A. Close Access
(1)
Make sure that the work area is clean and clear of tool(s) and other items.
(2)
Install the access panel/s (Ref. TASK 53-35-13-400-002).
(a)
FOR 10HM2
-191KB
-191BB,
(b)
FOR 11HM2