the total electrical resistance of the cable between the parking ground point and the grounding point on the landing gear must not be more than 500 milliohms.

 -
the resistance between the end connector on the ground cable and the nearest adjacent metal part of the landing gear must not be more than 10 milliohms.


 (1)
 Connect a ground cable to the aircraft grounding point on the landing gears. (Ref. Fig. 201/TASK 12-34-24-991-001, 202/TASK 12-34-24-991-002)

 (2)
 Connect a bonding cable between the fuel tanker and a grounding point on one of the MLG Legs or the NLG Leg, (Ref. Fig. 201/TASK 12-34-24-991-001, 202/TASK 12-34-24-991-002) or connect a bonding cable between the fuel tanker and the grounding point on the upper wing surface. (Ref. Fig. 203/TASK 12-34-24-991-003) The aircraft wheels must be on ground.


 5. Close-up
________
 Subtask 12-34-24-080-050
 A. Disconnect the ground cables.
 (1) After the refuel/defuel operations disconnect all grounding and bonding cables.
R 1EFF : 001-049, 101-149, 151-199, 201-299, 1 12-34-24Page 202 1301-399, 401-499, 1Aug 01/05 1 1 1CES 1


 Location of the Grounding Point on the Nose Landing Gear
 Figure 201/TASK 12-34-24-991-001

 

 Location of the Grounding Point on the Main Landing Gear
 Figure 202/TASK 12-34-24-991-002

 

 Grounding Point on the Wing Upper Surface
 Figure 203/TASK 12-34-24-991-003
 1EFF :  ALL  1  12-34-24 Page 205 
1  1  Feb 01/98
 1  1
 1CES  1


R **ON A/C 051-099,


R  TASK 12-34-24-869-001-A 
R  Aircraft Grounding for the Refuel/Defuel and Oxygen Servicing Operations 
R  WARNING : DO NOT WEAR A HEADSET OR TOUCH CABLES/LINES CONNECTED TO THE_______ 
R  AIRCRAFT, DURING BAD WEATHER CONDITIONS. LIGHTNING IS DANGEROUS. 
R  1. Reason for the Job__________________ 
R  To electrostatically balance the aircraft for the refuel/defuel and oxygen 
R  servicing operations. 

R  NOTE : Bonding is essential, grounding is recommended.____ 
R  2. Job Set-up Information______________________ 
R  A. Fixtures, Tools, Test and Support Equipment 
R  -------------------------------------------------------------------------------
R  REFERENCE  QTY DESIGNATION 
R  -------------------------------------------------------------------------------
R  No specific  bonding cable 
R  No specific  ground cable 
R  B. Referenced Information 
R  -------------------------------------------------------------------------------
R  REFERENCE  DESIGNATION 
R  -------------------------------------------------------------------------------
R  12-34-24-991-001  Fig. 201 
R  12-34-24-991-002  Fig. 202 
R  12-34-24-991-003  Fig. 203 
R  3. Job Set-up__________ 
R  Subtask 12-34-24-210-054 
R  A. Safety Precautions 
R  (1) Make sure that the fuel tanker or the oxygen ground filling 
R  equipement is grounded. 

R 1EFF : 051-099, 1 12-34-24Page 206 1 1 May 01/05 1 1 1CES 1

R 4. Procedure
_________

R  Subtask 12-34-24-869-053 
R  A. Connection of the Ground Cables 
R  WARNING : ALWAYS CONNECT THE GROUND CABLE TO THE PARKING GROUND POINT_______ 
R  BEFORE YOU CONNECT IT TO THE AIRCRAFT. DO NOT ATTACH THE CABLE 
R  TO THE AIRCRAFT FIRST (THERE IS A RISK OF ELECTRIC SHOCK). 
R  NOTE : For the satisfactory removal of an electrical charge from the____ 
R  aircraft: 
R  - the aircraft ground cable must have a section of 22 mm2 (0.0033 
R  in2) or more. 
R  - the total electrical resistance of the cable between the parking 
R  ground point and the grounding point on the landing gear must 
R  not be more than 500 milliohms. 
R  - the resistance between the end connector on the ground cable and 
R  the nearest adjacent metal part of the landing gear must not be 
R  more than 10 milliohms. 
R  (1) Connect a ground cable to the aircraft grounding point on one of the 
R  MLG legs or the NLG leg, 
R  (Ref. Fig. 201/TASK 12-34-24-991-001, 202/TASK 12-34-24-991-002) 
R  (2) Connect a bonding cable between the fuel tanker or the oxygen ground 
 