The switch on the standby-pack-temperature controller has seven positions to test the components or the different operations of the controller. When the switch is pushed, a light will show the condition of the selected component for each air cooling pack. The GO light means there is not a failure. The NO GO light means that the selected component is failed. Here is a list what the controller monitors for each position of the switch: 1) Position 1 - the controller's power supply and bridge
reference.
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
21-51-00
ALL ú ú 08 Page 53 ú Mar 20/89
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
757 MAINTENANCE MANUAL
2) Position 2 - the maximum compressor temperature output current. 3) Position 3 - the maximum cooling pack temperature output
current. 4) Position 4 - the minimum output current. 5) Position 5 - the 50 percent output current. 6) Position 6 - the standby-pack-temperature sensor for a
shorted or open circuit, or an aircraft wiring problem.
7) Position 7 - the standby-compressor-outlet-temperature sensor for a shorted or open circuit, or an aircraft wiring problem.
(b) Do the standby pack temperature controller BITE test. 1) Supply the electric power. 2) Put the applicable (L or R) PACK control selectors, on the
P5 panel, to STBY-N. 3) Push all of the GO and the NO GO lights, on the controller.
Make sure each one of them come on. 4) Turn the test switch, on the controller, to position 1. 5) Push the test switch. Make sure the GO light comes on. 6) Do the two steps before this one for the test positions 2
through 7.
C. Control (Fig. 18)
(1)
To put the cooling pack system into operation, do these steps:
(a)
Make sure these circuit breakers, on the pilot's-overhead-circuit-breaker panel P11, are closed: 1) LEFT PACK AUTO POWER 2) LEFT PACK STANDBY POWER 3) LEFT PACK AUTO CONT 4) LEFT PACK STANDBY CONT 5) LEFT PACK FLOW CONT 6) RIGHT PACK AUTO POWER 7) RIGHT PACK STANDBY POWER 8) RIGHT PACK AUTO CONT 9) RIGHT PACK STANDBY CONT 10) RIGHT PACK FLOW CONT
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
21-51-00
ALL ú ú 10 Page 54 ú Mar 20/89
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
757
MAINTENANCE MANUAL
FLT COMPT
AIR CONDITIONING CONTROL MODULE
Cooling Pack Control
Figure 18
EFFECTIVITYùùùùùùùùùùùùùùùùùùùùùùùùùùùùùù. ú
21-51-00
ALL ú
ú 07 Page 55
ú Mar 20/89
BOEING PROPRIETARY - Copyright (C) - Unpublished Work - See title page for details.
A
757
MAINTENANCE MANUAL
(b)
Supply the electrical power (Ref 24-22-00).
(c)
Supply the pneumatic power (AMM 36-00-00/001).
(d)
Push the ECS/MSG button on the EICAS MAINT module on the pilot's-right-side panel P61. 1) Make sure the maintenance messages L or R PACK BITE are not
shown on the EICAS display. 2) Make sure the advisory messages L and R PACK OFF are shown on the EICAS display.