R NOTE : As the APU GEN was set to OFF because of a true failure, the fault
____ R confirmation is not necessary.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page C245
Aug 01/05 CES
R 4. Fault Isolation
_______________
R A. If the fault symptom is identified by the upper ECAM-DU warning APU GEN R FAULT and one of these two CMS messages: R DELTA CURRENT GEN APU CHANNEL or R OVERCURRENT GEN APU CHANNEL
R NOTE : This CFDS messages can come into view with other CFDS messages
____ R related to a delta current or an overcurrent condition of one of R the generator channels 1 or 2.
R - do the trouble shooting procedure related to the delta current or the R overcurrent condition messages.
R NOTE : When you do the trouble shooting for the CFDS message DELTA
____ R CURRENT GEN APU CHANNEL or OVERCURRENT GEN APU CHANNEL, you can R remove one after the other the GCU 1 and the GCU 2 from their R position in the forward avionics rack 90VU to isolate the main AC R buses 1XP and 2XP.
R (1) If the fault continues:
R - do a check of the feeders (Ref. ASM 24-23/01) for a short circuit
R or a short to ground between:
R . feeder A pin L1 of the APU generator AC current transformer R (42XS) and pin A/F of the APU GLC (3XS)
R . feeder B pin L2 of the APU generator AC current transformer and R pin A/E of the APU GLC
R . feeder C pin L3 of the APU generator AC current transformer and R pin A/D of the APU GLC.
R (a) If the feeders are not correct:
R - repair or replace the feeders as necessary.
R (b) If the feeders are correct:
R - do a check and repair the feeders between the APU GLC (3XS),
R the EPC (3XG), the BTC 1 (11XU1) and the BTC 2 (11XU2) (Ref.
R ASM 24-22/02), (Ref. ASM 24-22/03) and (Ref. ASM 24-41/01).
R B. Open, safety and tag this(these) circuit breaker(s):
R -------------------------------------------------------------------------------R PANEL DESIGNATION IDENT. LOCATION
R -------------------------------------------------------------------------------R 122VU ELEC/GCU/2 2XU2 T27
R C. If the feeders are correct:
R - loosen and lower the nuts that attach the GCU 2 and pull it from the
R forward electronics rack 90VU to disconnect the electrical connectors
R - energize the aircraft electrical circuits from the APU (Ref. AMM TASK
R 24-41-00-861-002)
R - after five minutes, see if there is a trip.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page C246
Aug 01/05 CES
R (1) If there is a trip:
R - de-energize the aircraft electrical circuits from the APU (Ref. AMM
R TASK 24-41-00-862-002)
R - do the trouble shooting of the generator 1 channel (Ref. TASK 24-
R 20-00-810-862).
R (2) If there is no trip:
R - push the GCU 2 on its rack to connect the electrical connectors and
R engage the nuts on the lugs and tighten. Then on the rear circuit
R breaker panel 122VU, remove the safety clip and tag and close the
R circuit breaker 2XU2
R - after five minutes, see if there is a trip.
R (a) If there is a trip:
R - de-energize the aircraft electrical circuits from the APU (Ref.
R AMM TASK 24-41-00-862-002)
R - do the trouble shooting of the generator 2 channel (Ref. TASK
R 24-20-00-810-863).
R D. Make sure that the aircraft electrical circuits operate correctly in APU
R configuration.
R (1) Make sure that the GCU 1 and the GCU 2 are correctly installed on
R their forward electronics rack 90VU.
R (2) On the rear circuit breaker panel 122VU, make sure that the circuit
R breakers 2XU1 and 2XU2 are closed (if the circuit breakers are not
R closed, remove the safety clips and tags and close them).
R (3) Energize the aircraft electrical circuits from the APU (Ref. AMM TASK
R 24-41-00-861-002).
R (4) Let the APU generator operate for five minutes to make sure that it
R operates correctly.
R (5) De-energize the aircraft electrical circuits from the APU (Ref. AMM
R TASK 24-41-00-862-002).