R  Overload on the Electrical Network of the Generator 1 
R  1. Possible Causes_______________ 
R  - MAIN/GALLEY C/PWR/SPLY (1MC) 
R  - AFTER GALLEY FEEDER B (12MC) 
R  - wiring 
R  2. Job Set-up Information______________________ 
R  A. Referenced Information 
R  -------------------------------------------------------------------------------
R  REFERENCE  DESIGNATION 
R  -------------------------------------------------------------------------------

R  AMM  24-41-00-861-002 

R  AMM  24-41-00-862-002 

R  AMM  71-00-00-710-003 
R  AMM  71-00-00-710-028 
R  AMM  71-00-00-710-043 
R  ASM  24-51/02 

R 3. Fault Confirmation
__________________ R A. Job Set-up
Energize the Aircraft Electrical Circuits from the External Power De-energize the Aircraft Electrical Circuits Supplied from the External Power Engine Automatic Start Engine Shutdown Normal Engine Automatic Start Procedure
R (1) Aircraft Maintenance Configuration

R (a) Energize the aircraft electrical circuits from the external power
R (Ref. AMM TASK 24-41-00-861-002).
R (2) On the ELEC panel 35VU, make sure that the ELEC/GEN 1 pushbutton

R switch (3XU1) is pushed.

R (3) On the ELEC panel 35VU, make sure that the ELEC/GALLEY pushbutton
R switch (2XA) is pushed (the OFF legend is off).
R B. Test
R (1) Start the engine 1 (Ref. AMM TASK 71-00-00-710-003).
R (2) On the upper ECAM DU, the warning GEN 1 OVERLOAD is shown.

 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page B293
 Aug 01/05 CES


R  4. Fault Isolation_______________ 
R  A. Table of the circuit breakers used in this procedure: 
R  -------------------------------------------------------------------------------
R  PANEL  DESIGNATION  IDENT. LOCATION 
R  -------------------------------------------------------------------------------
R  123VU BUS 1/131XP-A/SPLY  5XN1  AB12 
R  123VU BUS 1/103XP/SPLY  3XN1  AB11 
R  123VU TR1/SPLY  2PU1  AB10 
R  123VU B HYD/ELEC PUMP  2701GJ  AB09 
R  123VU AC ESS/BUS ON/BUS 1  1XC  AC12 
R  123VU BUS 1/101XP/SPLY  1XN1  AD11 
R  123VU AVNCS VENT/BLOWER/FAN  1HQ  AD10 
R  123VU BUS 1/110XP/SPLY  7XN1  AF11 
R  123VU ANTI ICE/L/WHSLD  1DG1  AF10 
R  B. If the test confirms the fault: 

R - in the AC power center panel 123VU, do a check of the circuit breakers
R 1MC and 12MC.

R (1) If the circuit breakers 1MC and/or 12MC are open:
R - replace the MAIN/GALLEY C/PWR/SPLY (1MC) and/or the AFTER GALLEY
R FEEDER B (12MC).

R (2) If the circuit breakers 1MC and 12MC are closed:
R - on the AC power center panel 123VU, do a check of the status of the
R circuit breakers 5XN1, 3XN1, 7XN1, 1DG1, 1XC, 2701GJ, 1HQ, 1XN1 and
R 2PU1.

R (a) If one or more circuit breaker(s) is(are) open:
R - do a check of the loads downstream of the open circuit
R breaker(s) for a short to ground or a defective component.

R (b) If all the circuit breakers are closed:
R - stop the engine 1 (Ref. AMM TASK 71-00-00-710-003)
R - de-energize the aircraft electrical network from the external
R power (Ref. AMM TASK 24-41-00-862-002) and do the procedure
R that follows.

R C. Do a check of the AC/DC main power center 120VU:
R - open the AC/DC main power center 120VU and do a check of the wiring for
R a short circuit or a short to ground between downstream of the GLC 1
R (load side) and the loads (Ref. ASM 24-51/02).

R (1) If the wiring is not correct:
R - repair or replace as necessary.

R (2) If the wiring is correct:
R - do a check of the feeders for a short to ground, a short circuit or
R a related defective equipement between the pins R, M, G, P, L, H,
R N, K and J of the GLC 1 and the load side (Ref. ASM 24-51/02).

 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page B294
 Aug 01/05 CES


R  (a) If there is a short to ground: 
R  - repair or replace as necessary. 
 