「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page C210
Aug 01/05 CES
R (5) Do this test:
R -------------------------------------------------------------------------------
R ACTION RESULT
R -------------------------------------------------------------------------------
R On the ECAM control panel: On the lower ECAM DU:
R - get the ELEC page. - the correct electrical parameters of
R the GEN 1 are shown and the AC1
R busbar is supplied by the GEN 1.
R 5. Close-up________
R A. Put the aircraft back to its initial configuration.
R (1) Stop the engine 1 (Ref. AMM TASK 71-00-00-710-028).
R (2) Do the EIS stop procedure
R (Ref. AMM TASK 31-60-00-860-002).
R (3) On the ECAM control panel, set the UPPER DISPLAY and LOWER DISPLAY
R potentiometers to OFF.
R (4) De-energize the aircraft electrical circuits
R (Ref. AMM TASK 24-41-00-862-002).
R TASK 24-20-00-810-925 R Failure of the GEN 2 Feeders or the Current Transformer Assembly R 1. Possible Causes
_______________
R - CT-AC, 2 (41XU2)
R - GCU-2 (1XU2)
R - feeders
R - wiring
R 2. Job Set-up Information
______________________
R A. Referenced Information
R -------------------------------------------------------------------------------R REFERENCE DESIGNATION R -------------------------------------------------------------------------------
R AMM 24-22-17-000-001 R R AMM 24-22-17-400-001 R R AMM 24-22-34-000-001 R AMM 24-22-34-400-001 R AMM 24-41-00-740-002 R AMM 24-41-00-861-002 R R AMM 24-41-00-862-002 R R AMM 31-60-00-860-001 R AMM 31-60-00-860-002 R AMM 71-00-00-710-003 R AMM 71-00-00-710-028 R ASM 24-22/01
R 3. Fault Confirmation
__________________
R A. Test
R Not applicable.
Removal of the AC Current Transformers (41XU1, 41XU2, 51XU1, 51XU2) Installation of the AC Current Transformers (41XU1, 41XU2, 51XU1, 51XU2) Removal of the GCU-1(2) (1XU1, 1XU2) Installation of the GCU-1(2) (1XU1, 1XU2) Operational Check of GAPCU via CFDS Energize the Aircraft Electrical Circuits from the External Power De-energize the Aircraft Electrical Circuits Supplied from the External Power EIS Start Procedure EIS Stop Procedure Engine Automatic Start Engine Shutdown
R NOTE : As the GEN 2 was set to OFF because of a true failure, the fault
____ R confirmation is not necessary.
R 4. Fault Isolation
_______________
R A. If the fault symptom is identified by the CFDS message WRG: GEN2 FEEDER/
R CTA (41XU2) and the upper ECAM-DU warning GEN 2 FAULT:
R - do a check of the feeders (Ref. ASM 24-22/01) for an open circuit
R between:
R . terminal block T1 of the IDG 2 and terminal 1 of the 1998VT
R . terminal block T2 of the IDG 2 and terminal 2 of the 1998VT
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page C212
Aug 01/05 CES
R . terminal block T3 of the IDG 2 and terminal 3 of the 1998VT.
R (1) If the feeders are not correct:
R - repair or replace the feeders as necessary.
R (2) If the feeders are correct:
R - do an electrical resistance test of the Current Transformer
R Assembly (CTA) (41XU2) between:
R . pins A and G (6.725 ohms plus or minus 2.075 ohms)
R . pins B and G (6.725 ohms plus or minus 2.075 ohms)