R (1) Aircraft Maintenance Configuration

R (a) Energize the aircraft electrical circuits
R (Ref. AMM TASK 24-41-00-861-002).

R (b) Do the EIS start procedure (Upper ECAM DU and lower ECAM DU only)
R (Ref. AMM TASK 31-60-00-860-001).

R (2) On the ELEC panel 35VU:
R - push, release and push again the GEN 2 pushbutton switch (3XU2).

R (3) Do the operational test of the GAPCU (Ref. AMM TASK 24-41-00-740-R 002).

R (4) Start the engine 2 (Ref. AMM TASK 71-00-00-710-003).

 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page B203
 Aug 01/05 CES

R (5) Do this test:


R  -------------------------------------------------------------------------------
R  ACTION  RESULT 
R  -------------------------------------------------------------------------------
R  On the ECAM control panel:  On the lower ECAM DU: 
R  - get the ELEC page.  - the correct electrical parameters of 
R  the GEN 2 are shown and the AC2 
R  busbar is supplied by the GEN 2. 
R  5. Close-up________ 
R  A. Put the aircraft back to its initial configuration. 
R  (1) Stop the engine 2 (Ref. AMM TASK 71-00-00-710-028). 
R  (2) Do the EIS stop procedure 
R  (Ref. AMM TASK 31-60-00-860-002). 
R  (3) On the ECAM control panel, set the UPPER DISPLAY and LOWER DISPLAY 
R  potentiometers to OFF. 
R  (4) De-energize the aircraft electrical circuits 
R  (Ref. AMM TASK 24-41-00-862-002).


R TASK 24-20-00-810-888


R Failure of an Opposite Channel of the Generator 1 Channel
R 1. Possible Causes_______________
R - feeders
R 2. Job Set-up Information______________________
R A. Fixtures, Tools, Test and Support Equipment
R -------------------------------------------------------------------------------R REFERENCE QTY DESIGNATION R -------------------------------------------------------------------------------
R No specific circuit breaker(s) safety clip(s)
R B. Referenced Information
R -------------------------------------------------------------------------------R REFERENCE DESIGNATION R -------------------------------------------------------------------------------
R 24-20-00-810-863 Failure of the Generator 2 Channel R AMM 24-41-00-740-002 Operational Check of GAPCU via CFDS R AMM 24-41-00-861-002 Energize the Aircraft Electrical Circuits from the R External Power R AMM 24-41-00-862-002 De-energize the Aircraft Electrical Circuits Supplied R from the External Power R AMM 31-60-00-860-001 EIS Start Procedure R AMM 31-60-00-860-002 EIS Stop Procedure R AMM 71-00-00-710-003 Engine Automatic Start R AMM 71-00-00-710-028 Engine Shutdown R ASM 24-22/02
R 3. Fault Confirmation__________________
R A. Test
R Not applicable.

R NOTE : As the GEN 1 was set to OFF because of a true fault, the fault

____ R confirmation is not necessary.
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : 401-499, ∞∞24-20-00∞∞∞∞∞∞∞∞∞∞Page B205
 Aug 01/05 CES

R 4. Fault Isolation
_______________

R A. If the fault symptom is identified by the upper ECAM-DU warning AC BUS 1 R FAULT and one of the two CFDS messages: R GEN 1 DELTA CURRENT OTHER CHANNEL or R GEN 1 OVERCURRENT OTHER CHANNEL
R NOTE : These CFDS messages can come into view with other CFDS messages
____ R related to a delta current or an overcurrent condition of one of R the generator channels 1 or 2.
R - in the AC/DC main power center 120VU, do a check of the bus tie feeders
R for short circuits.

R (1) If there are short circuits:
R - repair them.

R (2) If there is no short circuit:
R - do a check of the feeders for a short to ground, a short circuit or
R an open circuit condition between terminals R, P, N of the BTC 1
R and the AC transfer bus (Ref. ASM 24-22/02).

R (a) If the feeders are not correct:
R - repair or replace the AC transfer busbars as necessary.

R (b) If the feeders are correct:
R - continues the trouble shooting.

R B. Open, safety and tag this(these) circuit breaker(s):

R -------------------------------------------------------------------------------R PANEL DESIGNATION IDENT. LOCATION
R -------------------------------------------------------------------------------R 122VU ELEC/GCU/1 2XU1 T26

R C. Energize the aircraft electrical circuit from the generator 2 only.
 