A. Put the aircraft back to its initial configuration.
(1) Close the circuit breaker (5FP1).
(2) On the panel 25VU, set the ANN LT switch to BRT.
(3) Do the ADIRS stop procedure (Ref. AMM TASK 34-10-00-860-005).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞34-13-00∞∞∞∞∞∞∞∞∞∞Page A230
Feb 01/05R
CES The FAULT Legend of the ADR2 Annunciator does not come on while the related Warning is shown on the Upper ECAM DU
1. Possible Causes
_______________
- ADIRU-2 (1FP2)
- BOARD-ANN LT TEST & INTFC (19LP)
- CDU-ADIRS (2FP)
- wiring of the ADR FAULT WARN discrete from the ADIRU2 (1FP2) to the annunciator light test and interface board (19LP)
- wiring of the annunciator light test and interface board (19LP)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 33-14-33-000-001 Removal of the Annunciator-Light Test and Interface-Board (1LP, 2LP, 3LP, 4LP, 5LP, 6LP, 7LP, R 8LP, 9LP, 10LP, 11LP, 12LP, 18LP, 19LP, 20LP) AMM 33-14-33-400-001 Installation of the Annunciator-Light Test and Interface-Board (1LP, 2LP, 3LP, 4LP, 5LP, 6LP, 7LP,
R 8LP, 9LP, 10LP, 11LP, 12LP, 18LP, 19LP, 20LP) AMM 34-10-00-860-002 ADIRS Start Procedure AMM 34-10-00-860-005 ADIRS Stop Procedure AMM 34-12-12-000-001 Removal of the ADIRS CDU (2FP) AMM 34-12-12-400-001 Installation of the ADIRS CDU (2FP) AMM 34-12-34-000-001 Removal of the ADIRU (1FP1, 1FP2, 1FP3) AMM 34-12-34-400-001 Installation of the ADIRU (1FP1, 1FP2, 1FP3) ASM 34-13/02
3. Fault Confirmation
__________________
A. Job Set-Up
(1) Do the ADIRS start procedure (Ref. AMM TASK 34-10-00-860-002).
B. Table of the circuit breakers used in this procedure:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
**ON A/C 001-049, 051-061, 101-105, 201-203,
121VU ADIRS/ADIRU/2/26VAC AND AOA 5FP2 N09
R **ON A/C 062-099, 106-149, 151-199, 204-299, 301-399, 401-499,
121VU ADIRS/ADIRU/2/26VAC AND AOA 5FP2 N08
**ON A/C ALL
C. Test
-------------------------------------------------------------------------------ACTION RESULT -------------------------------------------------------------------------------
1. Open the circuit breaker (5FP2). - on the upper ECAM DU, the NAV ADR 2 FAULT warning comes into view
- on the ADIRS CDU, the FAULT legend of the ADR2 annunciator comes on.
4. Fault Isolation
_______________
A. If the FAULT legend of the ADR2 annunciator does not come on:
- on the panel 25VU, set the INT LT/ANN LT switch to TEST and make sure that the FAULT legend comes on.
(1) If the FAULT legend comes on:
- replace the ADIRU-2 (1FP2) (Ref. AMM TASK 34-12-34-000-001) and (Ref. AMM TASK 34-12-34-400-001).
(a) If the FAULT legend stays off while the ECAM warning is shown:
- replace the BOARD-ANN LT TEST & INTFC (19LP) (Ref. AMM TASK 33-14-33-000-001) and (Ref. AMM TASK 33-14-33-400-001).
1 If the fault continues:
_
- do a check and repair the wiring of the ADR FAULT WARN discrete from the ADIRU2 (1FP2) to the annunciator light test and interface board (19LP) (Ref. ASM 34-13/02).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞34-13-00∞∞∞∞∞∞∞∞∞∞Page A232
Aug 01/05 CES (2) If the FAULT legend does not come on:
- replace the BOARD-ANN LT TEST & INTFC (19LP) (Ref. AMM TASK 33-14-33-000-001) and (Ref. AMM TASK 33-14-33-400-001).
(a) If the fault continues:
- replace the CDU-ADIRS (2FP) (Ref. AMM TASK 34-12-12-000-001) and (Ref. AMM TASK 34-12-12-400-001).
1_ If the fault continues:
- do a check and repair the wiring of the annunciator light
test and interface board (19LP)