(b) If there is no 26VAC:
- do a check for a ground signal at pins AC/4, 9 of the ADIRU 1 (1FP1).
1 If there is no ground signal:
_
- repair the wiring between ADIRU 1 pins AC/4,9 and the ground terminal (Ref. ASM 34-11/01).
2 If there is a ground signal:
_
- do a check of the wiring between ADIRU 1 pins AC/10, 6 and the circuit breaker (5FP1) (Ref. ASM 34-11/01).
a If there is no continuity:
_ - repair the above wiring.
b If there is continuity:
_ - replace the C/B-ADIRU/AOA 1 26VAC (5FP1).
(2) If the circuit breaker (5FP1) is open:
- close the circuit breaker.
(a) If the circuit breaker trips:
- replace the ADIRU-1 (1FP1) (Ref. AMM TASK 34-12-34-000-001) and (Ref. AMM TASK 34-12-34-400-001).
1 If the fault continues:
_
- do a check for a short to ground at the wiring between ADIRU 1 pins AC/10, 6 and the circuit breaker (5FP1) (Ref. ASM 34-11/01).
a If there is a short to ground:
_ - repair the above wiring.
b If there is no short to ground:
_ - replace the C/B-ADIRU/AOA 1 26VAC (5FP1).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞34-11-00∞∞∞∞∞∞∞∞∞∞Page 202
May 01/05 CESR **ON A/C 051-099, 106-149, 204-299, 301-399, 401-499,
A. If the test gives the maintenance message AOA SENSOR1 (3FP1) SPLY :
(1) If the circuit breaker (5FP1) is closed:
- do a check for 26VAC at pins AC/10, 6 of the ADIRU 1 (1FP1).
(a) If there is 26VAC:
- replace the ADIRU-1 (1FP1) (Ref. AMM TASK 34-12-34-000-001) and (Ref. AMM TASK 34-12-34-400-001).
(b) If there is no 26VAC:
- do a check for a ground signal at pins AC/4, 9 of the ADIRU 1 (1FP1).
1 If there is no ground signal:
_
- repair the wiring between ADIRU 1 pins AC/4,9 and the ground terminal (Ref. ASM 34-11/01).
2 If there is a ground signal:
_
- do a check of the wiring between ADIRU 1 pins AC/10, 6 and the circuit breaker (5FP1) (Ref. ASM 34-11/01).
a If there is no continuity:
_
- repair the above wiring. b If there is continuity:
_ - replace the C/B-ADIRU/AOA 1 26VAC (5FP1).
(2) If the circuit breaker (5FP1) is open:
- close the circuit breaker.
(a) If the circuit breaker trips:
- replace the ADIRU-1 (1FP1) (Ref. AMM TASK 34-12-34-000-001) and (Ref. AMM TASK 34-12-34-400-001).
1 If the fault continues:
_
- do a check for a short to ground at the wiring between ADIRU 1 pins AC/10, 6 and the circuit breaker (5FP1) (Ref. ASM 34-11/01).
a If there is a short to ground:
_
- repair the above wiring. b If there is no short to ground:
_
- replace the C/B-ADIRU/AOA 1 26VAC (5FP1).
**ON A/C ALL
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞34-11-00∞∞∞∞∞∞∞∞∞∞Page 203
Aug 01/05 CES
Loss of the 26VAC Power Supply of the ADIRU 2
1. Possible Causes
_______________
- ADIRU-2 (1FP2)
- wiring
- C/B-ADIRS/ADIRU/2/26VAC AND AOA (5FP2)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 34-12-34-000-001 Removal of the ADIRU (1FP1, 1FP2, 1FP3)
AMM 34-12-34-400-001 Installation of the ADIRU (1FP1, 1FP2, 1FP3)
AMM 34-13-00-740-002 INTERFACE TEST of the ADR
ASM 34-11/01
3. Fault Confirmation
__________________
A. Table of the circuit breakers used in this procedure:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
**ON A/C 001-049, 051-061, 101-105, 201-203,
121VU ADIRS/ADIRU/2/26VAC AND AOA 5FP2 N09 R **ON A/C 062-099, 106-149, 151-199, 204-299, 301-399, 401-499,
121VU ADIRS/ADIRU/2/26VAC AND AOA 5FP2 N08 **ON A/C ALL
B. Test
(1) Do the Interface test of the ADR (system 2) (Ref. AMM TASK 34-13-00-740-002).
(a) If you cannot close the circuit breaker (5FP2), go to Para. 4.A.(2).