A. Test Do the Interface test of the ADR (system 3) (Ref. AMM TASK 34-13-00-740-002).
4. Fault Isolation
_______________
R **ON A/C 001-049, 101-105, 151-199, 201-203,
A. If the test gives the maintenance message WRG: ACFT IDENT PIN PROG:
- remove the ADIRU-3 (1FP3) (Ref. AMM TASK 34-12-34-000-001)
- do a check of the aircraft identification-code programming-pins AA/1E, 1F, 1G, 1H, 1J, 1K, 2E, 4A, 4B on the rack connector
- compare the state of the aircraft identification-code pin-programming with the state given in the ASM (Ref. ASM 34-12/03).
(1) If the pin-programming is incorrect:
- repair the defective wiring of the rack connector
- install the ADIRU3 (Ref. AMM TASK 34-12-34-400-001).
(2) If the pin-programming is correct:
- install a new ADIRU3.
R **ON A/C 051-099, 106-149, 204-299, 301-399, 401-499,
A. If the test gives the maintenance message WRG: ACFT TYPE PIN PROG/ ADIRU3 (1FP3):
- remove the ADIRU-3 (1FP3) (Ref. AMM TASK 34-12-34-000-001)
- do a check of the aircraft identification-code programming-pins AA/1E, 1F, 1G, 1H, 1J, 1K, 2E, 4A, 4B on the rack connector
- compare the state of the aircraft identification-code pin-programming with the state given in the ASM (Ref. ASM 34-12/03).
(1) If the pin-programming is incorrect:
- repair the defective wiring of the rack connector
- install the ADIRU3 (Ref. AMM TASK 34-12-34-400-001).
(2) If the pin-programming is correct:
- install a new ADIRU3.
**ON A/C ALL
B. Do the test given in Para. 3.
Failure of the ADR1-SDI Pin-Programming
1. Possible Causes
_______________
- ADIRU-1 (1FP1)
- ADM-L TOTAL PRESSURE (19FP1)
- ADM-R STATIC PRESSURE (19FP4)
- ADM-L STATIC PRESSURE (19FP5)
- aircraft wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 34-11-17-000-001 Removal of the Air Data Module (19FP1,19FP2,19FP3,19FP4,19FP5,19FP6, 19FP7,19FP8) AMM 34-11-17-400-001 Installation of the Air Data Module
(19FP1,19FP2,19FP3,19FP4,19FP5,19FP6, 19FP7,19FP8) AMM 34-12-34-000-001 Removal of the ADIRU (1FP1, 1FP2, 1FP3) AMM 34-12-34-400-001 Installation of the ADIRU (1FP1, 1FP2, 1FP3) AMM 34-13-00-740-002 INTERFACE TEST of the ADR ASM 34-12/01 ASM 34-13/03
3. Fault Confirmation
__________________
A. Test Do the Interface test of the ADR (system 1) (Ref. AMM TASK 34-13-00-740-002).
4. Fault Isolation
_______________
R **ON A/C 001-049, 101-105, 151-199, 201-203,
A. If the test gives the maintenance message WRG: SDI PIN PROG:
- remove the ADIRU-1 (1FP1), (Ref. AMM TASK 34-12-34-000-001)
- do a check of pins AB/1A,5A,6A on the rack connector.
- compare the state of the pins with the SDI PIN PROGRAMMING given in the ASM (Ref. ASM 34-12/01).
(1) If the pin programming is incorrect:
- repair the aircraft wiring: defective pins
- install the ADIRU1 (Ref. AMM TASK 34-12-34-400-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞34-13-00∞∞∞∞∞∞∞∞∞∞Page A296
May 01/05 CES (2) If the pin programming is correct:
- swap the ADIRU1 and the ADIRU2.
(a) If the fault stops:
- replace the ADIRU that you installed on side 2.
(b) If the fault continues:
- get access to the ADM-L TOTAL PRESSURE (19FP1) (Ref. AMM TASK 34-11-17-000-001) (Para. 2.B.)
- disconnect the electrical connector of the ADM (19FP1)
- make sure that there is continuity between pins A/J,K and that there is an open circuit between pins A/L,M,N,P.
1 If the pin programming is incorrect:
_
- repair the aircraft wiring (Ref. ASM 34-13/03)
- connect the electrical connector of the ADM (19FP1)
- install the ADIRU1.
2 If the pin programming is correct:
_
- get access to the ADM-R STATIC PRESSURE (19FP4) ADM-L STATIC PRESSURE (19FP5), (Ref. AMM TASK 34-11-17-000-001) (Para. 2.B.)
- disconnect the electrical connector of the ADM (19FP4) 中国航空网 www.aero.cn 航空翻译 www.aviation.cn 本文链接地址:A320 Trouble Shooting Manual 排故手册 导航 NAVIGATION 1(112)