- disconnect the electrical connector of the ADM (19FP2)
- make sure that there is continuity between pins A/J, L and that there is an open circuit between pins A/K, M, N, P (Ref. ASM 34-13/03).
(a) If the pin programming is incorrect:
- repair the SDI pin programming of the ADM (19FP2)
- connect the electrical connector of the ADM (19FP2)
- install the ADIRU2.
(b) If the pin programming is correct:
- install a new ADIRU2
- connect the electrical connector of the ADM (19FP2).
1 If the fault continues:
_
- replace the ADM-R TOTAL PRESSURE (19FP2) (Ref. AMM TASK 34-11-17-000-001) and (Ref. AMM TASK 34-11-17-400-001).
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 051-099, 106-149, 204-299, 301-399, ∞∞34-13-00∞∞∞∞∞∞∞∞∞∞Page B212
401-499, Aug 01/05 CES
Disagree between ADIRU3 and ADM3 SDI Codes
1. Possible Causes
_______________
- ADIRU-3 (1FP3)
- ADM-STBY TOTAL PRESSURE (19FP3)
- SDI pin programming of the ADIRU3
- SDI pin programming of the ADM (19FP3)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 34-11-17-000-001 Removal of the Air Data Module (19FP1,19FP2,19FP3,19FP4,19FP5,19FP6, 19FP7,19FP8) AMM 34-11-17-400-001 Installation of the Air Data Module
(19FP1,19FP2,19FP3,19FP4,19FP5,19FP6, 19FP7,19FP8) AMM 34-12-34-000-001 Removal of the ADIRU (1FP1, 1FP2, 1FP3) AMM 34-12-34-400-001 Installation of the ADIRU (1FP1, 1FP2, 1FP3) AMM 34-13-00-740-002 INTERFACE TEST of the ADR ASM 34-12/03 ASM 34-13/03
3. Fault Confirmation
__________________
A. Test Do the Interface test of the ADR (system 3) (Ref. AMM TASK 34-13-00-740-002).
4. Fault Isolation
_______________
A. If the test gives the maintenance message WRG: SDI PIN PROG/ ADM3
(19FP3)/ ADIRU3 (1FP3)
- remove the ADIRU-3 (1FP3) (Ref. AMM TASK 34-12-34-000-001)
- do a check of the SDI pin programming, pins AB/1A, 5A, 6A on the rack connector
- compare the state of the pins with the SDI pin programming given in the ASM (Ref. ASM 34-12/03).
(1) If the pin programming is incorrect:
- repair the SDI pin programming of the ADIRU3
- install the ADIRU3 (Ref. AMM TASK 34-12-34-400-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 051-099, 106-149, 204-299, 301-399, ∞∞34-13-00∞∞∞∞∞∞∞∞∞∞Page B213
401-499, Aug 01/05 CES
(2) If the pin programming is correct:
- get access to the ADM (19FP3) (Ref. AMM TASK 34-11-17-000-001) (Para. 2.B.)
- disconnect the electrical connector of the ADM (19FP3)
- make sure that there is continuity between pins A/J, K, L, P and that there is an open circuit between pins A/M, N (Ref. ASM 34-13/03).
(a) If the pin programming is incorrect:
- repair the SDI pin programming of the ADM (19FP3)
- connect the electrical connector of the ADM (19FP3)
- install the ADIRU3.
(b) If the pin programming is correct:
- install a new ADIRU3
- connect the electrical connector of the ADM (19FP3).
1 If the fault continues:
_
- replace the ADM-STBY TOTAL PRESSURE (19FP3) (Ref. AMM TASK 34-11-17-000-001) and (Ref. AMM TASK 34-11-17-400-001).
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 051-099, 106-149, 204-299, 301-399, ∞∞34-13-00∞∞∞∞∞∞∞∞∞∞Page B214
401-499, Aug 01/05 CES
Disagree between ADIRU1 and ADM5 SDI Codes
1. Possible Causes
_______________
- ADIRU-1 (1FP1)
- ADM-L STATIC PRESSURE (19FP5)
- SDI pin programming of the ADIRU1
- SDI pin programming of the ADM (19FP5)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------