TASK 24-24-00-810-804 R EMER GEN Voltage and Frequency Indications Lost or Incorrect
1. Possible Causes
_______________
R - CONTROL UNIT-CSM/G (1XE) R - CSM/G (8XE)
- wiring
- C/B-EMER GEN VOLT (27WV)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 24-24-00-710-001 R AMM 24-24-34-000-001 R AMM 24-24-34-400-001 R AMM 24-24-51-000-001 R R AMM 24-24-51-400-001 R R ASM 24-24/01 R ASM 24-35/01
3. Fault Confirmation
__________________
R A. Job Set-up
Operational Test of the Emergency Generation System
Removal of the CSM/G Control Unit (1XE)
Installation of the CSM/G Control Unit (1XE)
Removal of the Constant Speed Motor/Generator (CSM/G)
(8XE)
Installation of the Constant Speed Motor/Generator
(CSM/G) (8XE)
Do the operational test of the emergency generation system (Ref. AMM TASK 24-24-00-710-001).
R B. Test
R -------------------------------------------------------------------------------R ACTION RESULT R ------------------------------------------------------------------------------- 4. Fault Isolation
R 1. On the ECAM control panel: If on the lower ECAM DU, the voltage
R - push the ELEC key to get the indication or the frequency indication
R ELEC page. shows in amber:
R - do the trouble shooting given in
R Para. 4.B.
R If on the lower ECAM DU, amber crosses
R replace the voltage and the frequency
R indications:
R - do the trouble shooting given in
R Para. 4.C.
_______________
A. Table of the circuit breakers used in this procedure:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------106VU EMER/GEN/REF 27WV B05
R 106VU AC ESS/BUS/EMER/CNTOR/SPLY 15PC C08
R B. If the test confirms the fault:
R - replace the CONTROL UNIT-CSM/G (1XE) (Ref. AMM TASK 24-24-34-000-001)
R and (Ref. AMM TASK 24-24-34-400-001).
R (1) If the fault continues:
R - replace the CSM/G (8XE) (Ref. AMM TASK 24-24-51-000-001) and (Ref.
R AMM TASK 24-24-51-400-001).
R (2) If the fault continues:
R - do a check and repair the wiring (Ref. ASM 24-24/01) between:
R . the pin 2/D of the CSM/G (8XE) and the pin A/D of the CSM/G R control unit (1XE)
R . the pin 2/E of the CSM/G (8XE) and the pin A/E of the CSM/G R control unit (1XE)
R . the pin 2/F of the CSM/G (8XE) and the pin A/G of the CSM/G R control unit (1XE)
R . the pin 2/G of the CSM/G (8XE) and the pin A/H of the CSM/G R control unit (1XE)
R . the pin 2/H of the CSM/G (8XE) and the pin A/J of the CSM/G R control unit (1XE)
R (3) If the fault continues:
R - do a check and repair the wiring (Ref. ASM 24-24/01) between:
R . the pin A/S of the CSM/G control unit (1XE) and the pin T1 of the R GLC EMER (2XE)
R . the pin A/R of the CSM/G control unit (1XE) and the pin T2 of the R GLC EMER (2XE)
R . the pin A/P of the CSM/G control unit (1XE) and the pin T3 of the R GLC EMER (2XE).
R C. If the test confirms the fault:
R - do a check of the position of the circuit breaker (27WV).
R (1) If the circuit breaker is closed:
R - do a check for 115VAC at the pin 2 of the circuit breaker (27WV).
R (a) If there is 115VAC:
R - do a check and repair the wiring between (Ref. ASM 24-35/01):
R . the pin 2 of the circuit breaker (27WV) and the first branch R point
R . the branch point and the pin AE/8B of the SDAC1 (1WV1) and R the pin AE/8B of the SDAC2 (1WV2).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞24-24-00∞∞∞∞∞∞∞∞∞∞Page 205
Aug 01/00 CES (b) If there is no 115VAC:
- do a check and repair the wiring between the pin 1 of the circuit breaker (27WV) and the pin 1 of the circuit breaker (15PC) (Ref. ASM 24-35/01) .
(2) If the circuit breaker is open: