- wiring of the ELAC OWN bus from the FAC 2 (1CC2) to the first terminal block
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 22-66-34-000-002 Removal of the FAC (1CC1,1CC2)
AMM 22-66-34-400-002 Installation of the FAC (1CC1,1CC2)
AMM 22-96-00-710-001 Operational Test of the AFS
ASM 22-69/01
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
121VU FLIGHT CONTROLS/ELAC2/NORM/SPLY 15CE2 R20
B. Test
(1) Do the operational test of the AFS (Ref. AMM TASK 22-96-00-710-001) and read the result for the FAC 2.
4. Fault Isolation
_______________
A. If the test gives the maintenance message AFS: FAC2/ELAC2 BUS WIRG:
- replace the FAC-2 (1CC2), (Ref. AMM TASK 22-66-34-000-002) and (Ref. AMM TASK 22-66-34-400-002).
(1) If the fault continues:
- do a check and repair the wiring of the ELAC OWN bus from the FAC 2 (1CC2) to the first terminal block (Ref. ASM 22-69/01).
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞22-66-00∞∞∞∞∞∞∞∞∞∞Page 255
May 01/04 CES
R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 401-499,
TASK 22-66-00-810-845
Loss of the Reception of the ELAC OPP Bus by the FAC 2 MON or the FAC 2 COM
1. Possible Causes
_______________
- FAC-2 (1CC2)
- wiring of the ELAC OPP bus from the FAC 2 (1CC2) to the first terminal block
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 22-66-34-000-002 Removal of the FAC (1CC1,1CC2)
AMM 22-66-34-400-002 Installation of the FAC (1CC1,1CC2)
AMM 22-96-00-710-001 Operational Test of the AFS
ASM 22-69/01
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
49VU FLIGHT CONTROLS/ELAC1/NORM/SPLY 15CE1 B11
B. Test
(1) Do the operational test of the AFS (Ref. AMM TASK 22-96-00-710-001) and read the result for the FAC 2.
4. Fault Isolation
_______________
A. If the test gives the maintenance message AFS: FAC2/ELAC1 BUS WIRG:
- replace the FAC-2 (1CC2), (Ref. AMM TASK 22-66-34-000-002) and (Ref. AMM TASK 22-66-34-400-002).
(1) If the fault continues:
- do a check and repair the wiring of the ELAC OPP bus from the FAC 2 (1CC2) to the first terminal block (Ref. ASM 22-69/01).
B. Do the test given in Para. 3.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 001-049, 051-099, 101-149, 151-199, ∞∞22-66-00∞∞∞∞∞∞∞∞∞∞Page 256
201-299, 401-499, Aug 01/05 CES
R **ON A/C ALL
TASK 22-66-00-810-846
Loss of the Reception of the ELAC OWN Bus by the FAC 1
1. Possible Causes
_______________
- wiring between terminal block 1835VT18 pin V and terminal block 1831VT9 pin K
- wiring between terminal block 1835VT19 pin V and terminal block 1831VT9 pin C
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 22-91-00-710-001 Ground Scanning of the AFS
AWM 27-92-29
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed: