On the display of the Data LoadingSelector:
-FMGC1(2) NOT SELECTED indication is shown.
On the multipurpose disk drive unit:
-the < < MDDU READY > > indication is shown.


 -------------------------------------------------------------------------------
ACTION RESULT -------------------------------------------------------------------------------
11. Close the circuit breaker 10CA1
 and 10CA2, and wait for FMGC
 safety test.


R  **ON A/C 106-149, 151-199, 211-299, 301-399, 401-499,
 Post SB 22-1089 For A/C 151-199,211-212,
 Subtask 22-70-00-970-068-B
 A. Uploading of the FMGC
 NOTE : When the uploading of the FMGC is completed, you can use the XLOAD
____ function to load the other FMGC (Ref. TASK 22-70-00-610-009).
 NOTE : The uploading time for one full disk is twelve minutes
____
 approximately.

 NOTE : After the uploading operations, you must do a check of the
____ reference of the data loaded in the FMGC, on the MCDU.
 NOTE : The uploading procedure that follows is for the FMGC1. For the
____ FMGC2 procedure which is the same, refer to the data in parentheses.
 -------------------------------------------------------------------------------ACTION RESULT -------------------------------------------------------------------------------
1. On the overhead panel, on the  On the display of the Data Loading
 Data Loading Selector: Selector:

 -Set the ON/OFF switch to ON.  - DB/N
 PUSH NEXT/PREV
 indication is shown.

 On the MDDU:
 -The < < MDDU READY > > indication is shown.
 2. On the overhead panel:
 -Open the circuit breakers 10CA1
 and 10CA2.

 

 -------------------------------------------------------------------------------
ACTION RESULT -------------------------------------------------------------------------------
3. On the Data Loading Selector:  On the display of the Data Loading Selector:
 - Push the PREV or NEXT key until you get the indication of the FMGC that you can load  - FMGC1(2)NOT SELECTEDindication is shown
 - Push the SEL CTL key.  - FMGC1(2) SELECTED
 indication is shown.
 4. Use the applicable disk(s) from the disk storage box.
 5. On the MDDU:  On the MDDU:
 - Put the disk into the disk  - The READY indication comes into view
 drive.  - Then, the WAIT RESPONSE indication comes into view.
 6. On the overhead panel: - Close the circuit breaker 10CA1  On the MDDU:- The READY indication comes into view
 (10CA2).  - Then, the WAIT RESPONSE indication comes into view and, immediately after, the TRANSF IN PROG indication comes into view
 - the BUS n :xxxxxxx indication is
 shown after the FMGC safety test.
 NOTE : "n" is the number of the bus (1____ to 8) in transfer. "xxxxxx" is the number of
 remaining bytes. The uploading is completed only when TRANSF COMPLETE indication
 is shown.
 NOTE : If more than one disk is____ necessary for the uploading, the EJECT DISK and INSERT NEXT DISK
 indications show one after the
 other. They tell the operator to put a new disk into the MDDU. 

 

 -------------------------------------------------------------------------------
ACTION RESULT -------------------------------------------------------------------------------
7. On the MDDU:
-Eject the disk from the disk drive.
8. On the overhead panel, on the Data Loading Selector:
-Push the SEL CTL key.
9.
 Open (for more than 5 seconds) the circuit breaker 10CA1 (10CA2).

 10.
 On the Data Loading Selector:


 -Set the ON/OFF switch to OFF.
 11. Close the circuit breakers 10CA1 and 10CA2, and wait for FMGC safety test.
 **ON A/C 151-199, 201-212,
 Post SB 31-1130 For A/C 201-203,
 Subtask 22-70-00-970-068-A

 A. Uploading of the FMGC
 -When all the disks are loaded in the FMGC, the TRANSF COMPLETE indication comes into view.
On the MDDU:
-The < < MDDU READY > > indicationcomes into view.
On the display of the Data LoadingSelector:
-FMGC1(2) NOT SELECTED indication is shown.
 NOTE : This procedure is for FMGC1. For the FMGC2, which is identical,
____ use the indications between the parentheses.
 NOTE : After the loading of one of the FMGCs, you can use the CROSSLOAD
____ function (Ref. TASK 22-70-00-610-009) to directly put the data into the other FMGC.


 