LO = blown fuse fault detected, HI = normal
9 SUM Not used
10 /OVT Overtemperature fault indicator signal, output from module, open
collector, LO = Over temp fault detected, HI = normal
California Instruments 101
User Manual Compact i/iX Series
7.6.2 POWER BOARD
7.6.2.1 HIGH VOLTAGE DC INPUT
PINS NAME DESCRIPTION
E1 +250V_IN +250 Vdc @ <5 Adc, must be able to sink current from module
E2 HV_COM_IN Return for +/- 250V_IN
E3 -250V_IN -250 Vdc @ <5 Adc, must be able to sink current from module
7.6.2.2 HIGH VOLTAGE OUTPUT
PINS NAME DESCRIPTION
E4 HV_COM_OUT Return for E5 and E6
E5 OUTPUT_LEFT 0 – 150 Vac, 375 VA max from 120 Vac to 150 Vac, 3.13 Arms max
E6 OUTPUT_RIGHT Same as for E5
7.6.3 CONFIGURATION
The module may be configured to operate as two independent 375 VA LO RANGE half bridges or as
a single 750 VA dual range half/f of
each power module, configuratio
xchanged in the field, the i/iX comes factory configured for the
ull bridge. Because DIP switches are used to set the operation
n may only be performed manually.
Note: Unless a module was e
correct mode of operation and these dip-switch settings should normally not have to
be changed. This information is provided for reference only.
Only factory authorized personnel should use this information if needed.
7.6.3.1 DIP SWITCH SETTINGS
DIP SWITCH S1
DIP switch S1 selects which oscillator phase will drive each half bridge.
DIP SWITCH
POSITION
NAME FUNCTION
1 LA ON for LEFT = Phase A (LB, LC must be OFF)
2 RA ON for RIGHT = Phase A (RB, RC must be OFF)
3 LB ON for LEFT = Phase B (LA, LC must be OFF)
4 RB ON for RIGHT = Phase B (RA, RC must be OFF)
5 LC ON for LEFT = Phase C (LA, LB must be OFF)
6 RC ON for RIGHT = Phase C (RA, RB must be OFF)
California Instruments 102
User Manual Compact i/iX Series
DIP SWITCH S2 – 4 Positions
For 6005-701-1 control board (Assy rev G or lower) DIP switch S2 configures the source of the error
(Assy rev H or higher) have a 2 position S2 dip switch instead. See below.
amplifier drive signal for multiple module master/auxiliary systems. New versions of the 6005-701-1
control board
DIP SWITCH
POSITION
NAME FUNCTION
1 EL ON to connect External Left error amplifier signal to external cable.
systems. This switch must be OFF for any single module system.
This switch must be ON for all multiple module single-phase
2 EC ON to connect External Common amplifier signal to external cable.
This switch must be ON for all multiple module single-phase
systems. This switch must be OFF for any single module system.
3 IL ON to connect error amplifier signal of module’s LEFT amplifier the
master error amplifier signal. This switch must be ON for any single
module system, or if the module is a master in a multiple module
system. This switch must be OFF if the LEFT amplifier of the
module is auxiliary to a different master.
4 IC ON to connect common of module’s LEFT amplifier as the master
common signal. This switch must be ON for any single module
system. This switch must be OFF if the LEFT amplifier of the
module is auxiliary to a different master.
DIP SWITCH S2 – 2 Positions
For 6005-701-1 control board (Assy rev H or higher) DIP switch S2 configures the source of the error
amplifier drive signal for multiple module master/auxiliary systems. Older versions of the 6005-701-1
control board (Assy rev G or lower) have a 4 position S2 dip switch instead. See above.
DIP SWITCH
POSITION
NAME FUNCTION
1 IL ON to connect error amplifier signal of module’s LEFT amplifier the
master error amplifier signal. This switch must be ON for any single
module system, or if the module is a master in a multiple module
system. This switch must be OFF if the LEFT amplifier of the
module is auxiliary to a different master.
2 IC ON to connect common of module’s LEFT amplifier as the master
common signal. This switch must be ON for any single module
system. This switch must be OFF if the LEFT amplifier of the
module is auxiliary to a different master.
DIP SWITCH S3
DIP switch S3 selects whether the RIGHT amplifier of the module is independent or auxiliary to a
different master.
DIP SWITCH
POSITION
NAME FUNCTION
1 MRR ON = MasterRight. This switch must be ON for RIGHT amplifier to be
it’s own master. This switch must be OFF if RIGHT amplifier is
auxiliary to another master.
2 SLR ON = SlaveRight. This switch must be ON for RIGHT amplifier to be
an auxiliary (slave). This switch must be OFF if RIGHT amplifier is