- do a check and repair the wiring of the 28VDC and 28VDC GND signals at the FMGC1 connector (Ref. ASM 22-84/01)
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞22-11-00∞∞∞∞∞∞∞∞∞∞Page 201
Feb 01/98 CES (1) If the check is correct:
- replace the FMGC-1 (1CA1) and (Ref. AMM TASK 22-83-34-400-001).
B. If the circuit breaker (10CA1) is open:
- close this circuit breaker.
(1) If the circuit breaker (10CA1) trips:
- replace the FMGC-1 (1CA1) (Ref. AMM TASK 22-83-34-000-001) and (Ref. AMM TASK 22-83-34-400-001).
(a) If the fault continues:
- do a check for a short to ground between the circuit breaker (10CA1) and the FMGC 1 (1CA1) (Ref. ASM 22-84/01)
- do a check for a short to ground between the circuit breaker (10CA1) and the A/THR 1 relays (5CA1), (17CA1) and (18CA1) (Ref. ASM 22-31/01).
1_ If there is a short to ground:
- repair the above wirings.
2_ If there is no short to ground:
- replace the C/B-AUTO FLT/FMGC/1 (10CA1).
C. Do the test given in Para. 3.
Failure of the FMGC 2
1. Possible Causes
_______________
- FMGC-2 (1CA2)
- wiring of the 28VDC and 28VDC GND signals
- short to ground between the circuit breaker (10CA2) and the A/THR 2 relays (5CA2), (17CA2) and (18CA2)
- C/B-AUTO FLT/FMGC 2 (10CA2)
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------
REFERENCE DESIGNATION
-------------------------------------------------------------------------------
AMM 22-83-34-000-001 Removal of the FMGC (1CA1,1CA2)
AMM 22-83-34-400-001 Installation of the FMGC (1CA1,1CA2)
AMM 22-96-00-710-001 Operational Test of the AFS
ASM 22-31/01
ASM 22-84/01
3. Fault Confirmation
__________________
A. Make sure that this(these) circuit breaker(s) is(are) closed:
-------------------------------------------------------------------------------
PANEL DESIGNATION IDENT. LOCATION
-------------------------------------------------------------------------------
121VU AUTO FLT/FMGC/2 10CA2 M17
B. Test
(1) Do the operational test of the AFS (Ref. AMM TASK 22-96-00-710-001) and read the result for the FMGC 2.
(a) If the circuit breaker (10CA2) is open, refer to Para. 4.B.
4. Fault Isolation
_______________
A. If the circuit breaker (10CA2) is closed and if the test gives the maintenance message AFS : FMGC2:
- remove the FMGC-2 (1CA2) (Ref. AMM TASK 22-83-34-000-001)
- do a check and repair the wiring of the 28VDC and 28VDC GND signals at the FMGC2 connector (Ref. ASM 22-84/01)
(1) If the check is correct:
- replace the FMGC-2 (1CA2) and (Ref. AMM TASK 22-83-34-400-001).
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞22-11-00∞∞∞∞∞∞∞∞∞∞Page 203
Feb 01/98 CES B. If the circuit breaker (10CA2) is open:
- close this circuit breaker.
(1) If the circuit breaker (10CA2) trips:
- replace the FMGC-2 (1CA2) (Ref. AMM TASK 22-83-34-000-001) and (Ref. AMM TASK 22-83-34-400-001).
(a) If the fault continues:
- do a check for a short to ground between the circuit breaker (10CA2) and the FMGC 2 (1CA2) (Ref. ASM 22-84/01)
- do a check for a short to ground between the circuit breaker (10CA2) and the A/THR 2 relays (5CA2), (17CA2) and (18CA2) (Ref. ASM 22-31/01).
1_ If there is a short to ground:
- repair the above wirings.
2_ If there is no short to ground:
- replace the C/B-AUTO FLT/FMGC 2 (10CA2).
C. Do the test given in Para. 3.
Loss of the FMGC 1 Bus Feedback
1. Possible Causes
_______________
- FMGC-1 (1CA1)
- wiring of the FMGC OWN A (MON) bus from the FMGC 1 (1CA1) to the first terminal block
- wiring of the FMGC MON OUT (MON) bus on the FMGC 1 (1CA1)