20-00-02/70-00-01


Test Setup of Thermocouple Simulation
Figure 329

Inspection
Page 357 Apr 1/05 Copying, use or disclosure of information on this page is subject to proprietary restrictions.

20-00-02/70-00-01


Typical Thermocouple Installation
Figure 330

Inspection
Page 358 Apr 1/05 Copying, use or disclosure of information on this page is subject to proprietary restrictions.

20-00-02/70-00-01


Uncompensated Cold Junction
Thermocouple Simulation
Figure 331

Inspection
Page 359 Apr 1/05 Copying, use or disclosure of information on this page is subject to proprietary restrictions.
20-00-02/70-00-01
(5)  In previous example the desired input voltage (temperature) was known and the unwanted junction voltage was subtracted from the desired input in order to obtain the correct voltage for the thermocouple voltage source. In the following example, Equation 2, the voltage of the thermocouple voltage source is known, such as when a temperature switch point is being checked, and the temperature associated with it is to be determined.  In Equation 1 the desired input is Equation 2’s “unknown input”.
Equation 1
.
Existing Input
.. . . . . .

.. . . . . .
.. . . . . .

.. . . . . .

Desired
.. . . .

.
..... .
Input from
Thermocouple
Voltage Input
Temp
.

from
=

Unwanted
.
Equation 2
.
.
Voltage Junction Source
.

.
.

.

Existing Input
.. . . . . .

.. . . . . .
.. . . . . .

.. . . . . .

Unknown
.. . . .

.. . . .

Input from
ThermocoupleInput from
+

=

Temp Unwanted Voltage
..
.
(6)  Most electronic control temperature tolerances are on the order of ±20 to ±40F.  The temperature simulation circuit should be 10 times more accurate than the allowable tolerances for the electronic control. This means that the temperature simulation circuit
.
should be accurate to within ±2 to ±4F. This includes the errors in measurement of the room temperature for the cold junction voltage.
(7)  Referring to an alumel-chromel thermocouple table, note that the millivolt reading for 1000F is 22.251 mv and for 1001F is 22.274 mv. The difference for this 1F Delta is 0.023 millivolts or 23 microvolts. This indicates that the voltmeter used for the thermocouple simulation voltage should have an accuracy and resolution of 0.01 millivolts or 10 microvolts.  With such an accurate voltmeter, more error (1-1/2 to 3-1/2F) is allowed for the room temperature reading errors. Note that a 4F error in measuring the room temperature means a 4F error in calibrating the control.
Voltage Junction Source
.

.
.

.

Inspection
Page 360
Apr 1/05

20-00-02/70-00-01
N. Composite Material Components
(1) Check per Table 308.
Table 308.  Inspection/Check Criteria and Repair Limits for Composite Material Components.
MATERIAL COMPOSITION OR ITEM/TYPE OF DAMAGE  USABLE LIMITS  MAXIMUM REPAIR LIMITS 
LAMINATE 
Delamination  None permitted.  All must be repaired. Maximum repair limits: 25% of component total area. 
Cuts, Scratches, Blemishes  Any that does not expose fiber reinforcement.  All cuts that penetrate fiber reinforcement, or are visible or require further processing are repairable. 
Cracks  None permitted.  Surface resin crack that does not penetrate fiber reinforcement. Cracks in reinforcement are not acceptable. 
Frayed Surface  None permitted.  All must be repaired. Maximum repair limits: 25% of component total area. 
 