• 热门标签

当前位置: 主页 > 航空资料 > 机务资料 >

时间:2011-03-28 09:13来源:蓝天飞行翻译 作者:航空
曝光台 注意防骗 网曝天猫店富美金盛家居专营店坑蒙拐骗欺诈消费者

 - remove the FILTER-RECIRCULATION (4013HM) (Ref. AMM TASK 21-21-41-000-001).


 (1) If the recirculation fan (14HG) operates correctly:

 - do a check of the recirculation filter (4013HM) for contamination.
 (a) If the filter is clogged:

 - replace the FILTER-RECIRCULATION (4013HM) (Ref. AMM TASK 21-21-41-000-001) and (Ref. AMM TASK 21-21-41-400-001).

 (b) If the filter is not clogged:


 - install the FILTER-RECIRCULATION (4013HM) (Ref. AMM TASK 21-21-41-400-001).

 (2) If the recirculation fan (14HG) does not operate:


 - do a check of the P/BSW-VENTILATION/CAB FANS (4HG) and replace it if necessary (Ref. ASM 21-21/01).
 (a) If the fault continues:

 - do a check of the RELAY-FAN FAULT SUPPRESS (16HG) and replace it if necessary (Ref. ASM 21-21/01).

 (b) If the fault continues:

 - do a check of the RELAY-R FAN POWER (6HG) and replace it if necessary (Ref. ASM 21-21/01).

 (c) If the fault continues:

 - do a check of the RELAY-R FAN CONTROL (8HG) and replace it if necessary (Ref. ASM 21-21/01).

 (d) If the fault continues:

 - do a check of the RELAY-R FAN FAULT (9HG) and replace it if necessary (Ref. ASM 21-21/01).

 (e) If the fault continues:

 - replace the FAN-RECIRCULATION (14HG) (Ref. AMM TASK 21-21-51-000-001) and (Ref. AMM TASK 21-21-51-400-001).

 (f) If the fault continues:

 - do a check and repair the wiring (Ref. ASM 21-21/01) and (Ref. ASM 21-63/01) from:

 - the FAN (14HG) to the CB (3HG),

 - the FAN (14HG) to the CB (11HG),

 - the FAN (14HG) to ground,

 - the RELAY (8HG) to the RELAY (6HG),

 - the RELAY (8HG) to ground,

 


 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1R EFF : 401-499, ∞∞21-21-00∞∞∞∞∞∞∞∞∞∞Page 212
 Aug 01/05 CES


R  - the RELAY (9HG) to the RELAY (6HG), 
R  - the RELAY (9HG) to ground, 
R  - the RELAY (9HG) to the ACSC2 (57HH), 
R  - the RELAY (16HG) to the SW (4HG) and, 
R  - the RELAY (16HG) to ground. 
R  **ON A/C ALL
 B. Do the test as given in the Para. 3.A.

 

 TASK 21-21-00-810-804
 Cabin Recirculation Fault (SDAC 1 / SDAC 2)
 1. Possible Causes
_______________
 - SDAC-1 (1WV1)

 - SDAC-2 (1WV2)

 - wiring


 2. Job Set-up Information
______________________
 A. Referenced Information
 -------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 21-21-00-710-001 Operational Test of the Cabin Recirculation Fans 14HG

 and 15HG.
 AMM 31-55-34-000-001 Removal of the SDAC (1WV1,1WV2)
 AMM 31-55-34-400-001 Installation of the SDAC (1WV1,1WV2)
 ASM 21-21/01

 3. Fault Confirmation
__________________
 A. Do the operational test of the cabin recirculation fans 14HG and 15HG (Ref. AMM TASK 21-21-00-710-001).
 4. Fault Isolation
_______________
 A. If the ECAM upper DU gives the warning COND L+R CAB FAN FAULT, but no maintenance message comes on:
 (1) replace the SDAC-1 (1WV1) (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).

 (2) If the fault continues:

 - replace the SDAC-2 (1WV2) (Ref. AMM TASK 31-55-34-000-001) and (Ref. AMM TASK 31-55-34-400-001).

 (3) If the fault continues:

 - do a check and repair the wiring (Ref. ASM 21-21/01) between:

 - the P/BSW-VENTILATION/CAB FANS (4HG)A pin B3 and SDAC-1 (1WV1)AA pin 10G and,

 - P/BSW-VENTILATION/CAB FANS (4HG)A pin B3 and SDAC-2 (1WV2)AA pin 10G.

 


 B. Do the test as given in the Para. 3.A.
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞21-21-00∞∞∞∞∞∞∞∞∞∞Page 214
 Feb 01/05 CES


 AIR DISTRIBUTION AND RECIRCULATION - TASK SUPPORTING DATA
_________________________________________________________


 Air Distribution and Recirculation - Block Diagram
 Figure 301

 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞21-21-00∞∞∞∞∞∞∞∞∞∞Page 302
 Feb 01/98 CES
 
中国航空网 www.aero.cn
航空翻译 www.aviation.cn
本文链接地址:A320 Trouble Shooting Manual 排故手册 AIR CONDITIONING 空调1(56)