 5. Close-up
________
 A. Do the EIS stop procedure (Ref. AMM TASK 31-60-00-860-002).
 「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-63-82∞∞∞∞∞∞∞∞∞∞Page 240
 Aug 01/05R
 CES  Transfer of the ECAM DU Image on the CAPT ND not Possible

 


 1. Possible Causes
_______________
 - DMC-1 (1WT1)
 - DMC-3 (1WT3) R - SEL SW-ECAM/ND XFR (19WT)
 - SEL SW-ECAM/ND XFR (19WT)

 - wiring


 2. Job Set-up Information
______________________
 A. Referenced Information
 -------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 31-60-00-860-001 EIS Start Procedure
 AMM 31-60-00-860-002 EIS Stop Procedure
 AMM 31-63-34-000-001 Removal of the DMC (1WT1,1WT2,1WT3)
 AMM 31-63-34-400-001 Installation of the DMC (1WT1,1WT2,1WT3)

R  ASM 31-68/01 ASM 31-68/03
 3. Fault Confirmation
__________________
 A. Job Set-up
 (1) Do the EIS start procedure (Ref. AMM TASK 31-60-00-860-001).

 (2) When the images come into view on the six display units:


 - set the ECAM/ND XFR selector switch (19WT) on the panel 8VU to CAPT.
 B. Test
 Make sure that the transfer is not possible.

 

 4. Fault Isolation
_______________


R **ON A/C 001-049, 051-099, 101-149, 151-199, 201-299, 301-399,
 A. If the EIS DMC selector switch (18WT) is at NORM and if you cannot get the ECAM DU image on the CAPT ND:
 - replace the SEL SW-ECAM/ND XFR (19WT).
 (1) If the fault continues:
 - do a check for a ground signal at pins AB/4B, 8J of the DMC1 (1WT1).
 (a) If there is no ground signal:
 - do a check for a ground signal at pin 5 of the ECAM/ND XFR selector switch (19WT).
 1 If there is no ground signal:
_

 - repair the wiring from ECAM/ND XFR selector switch (19WT) pin 5 to the ground terminal (Ref. ASM 31-68/03).
 2 If there is a ground signal:
_

 - do a check and repair the wiring from ECAM/ND XFR selector switch (19WT) pin 6 to DMC1 (1WT1) pin AB/4B, 8J.
 (b) If there is a ground signal:
 - replace the DMC-1 (1WT1) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001) (Ref. ASM 31-68/03).
 B. If the EIS DMC selector switch (18WT) is at CAPT/3 and if you cannot get the ECAM DU image on the CAPT ND:
 - replace the SEL SW-ECAM/ND XFR (19WT).
 (1) If the fault continues:
 - do a check for a ground signal at pin AB/4B of the DMC3 (1WT3).
 (a) If there is no ground signal:
 - do a check for a ground signal at pin 5 of the ECAM/ND XFR selector switch (19WT).
 1 If there is no ground signal:
_

 - repair the wiring from ECAM/ND XFR selector switch (19WT) pin 5 to the ground terminal (Ref. ASM 31-68/03).
 2 If there is a ground signal:
_

 - do a check and repair the wiring from ECAM/ND XFR selector switch (19WT) pin 6 to DMC3 (1WT3) pin AB/4B.

 

 (b) If there is a ground signal:

 - do a check for a ground signal at pin AB/8J of the DMC3 (1WT3).
 1 If there is no ground signal:
_

 - do a check for a ground signal at pin 13 of the EIS DMC selector switch (18WT).
 a If there is no ground signal:
_

 - repair the wiring from EIS DMC selector switch (18WT) pin 13 to the ground terminal.
 b If there is a ground signal:
_

 - do a check and repair the wiring from ECAM/ND XFR selector switch (19WT): . pin 16 to EIS DMC selector switch (18WT) pin 16 . pin 13 to DMC3 (1WT3) pin AB/8J.
 2 If there is a ground signal:
_

 - replace the DMC-3 (1WT3) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001).
R **ON A/C 401-499,
 A. If the EIS-DMC selector switch (18WT) is at NORM and you cannot get the image on the CAPT ND DU:
 - do a check for a ground signal at the pin AE-4D of the DMC1 (1WT1)
 (1) If there is a ground signal:

 - replace the DMC-1 (1WT1) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001).

 (2) If there is no ground signal :


 - do a check and repair the wiring from the pin AE-4G of the DMC1 (1WT1) to the first terminal block (Ref. ASM 31-68/01)
 B. If the EIS-DMC selector switch (18WT) is at CAPT/3 and you cannot get the image on the CAPT ND DU:
 