(2WT1,2WT2,3WT1,3WT2,4WT1,4WT2)
AMM 31-63-34-000-001 Removal of the DMC (1WT1,1WT2,1WT3)
AMM 31-63-34-400-001 Installation of the DMC (1WT1,1WT2,1WT3)
ASM 31-61/04
3. Fault Confirmation
__________________
A. Test
Do the EIS input test (Ref. AMM TASK 31-60-00-740-002).
4. Fault Isolation
_______________
A. If the test gives the maintenance message DMC1 : ATT DSPLY ERR:
- on the panel 301VU, push the CAPT PFD/ND XFR pushbutton switch (9WT1) to get the PFD image on the CAPT ND
- do the test given in Para. 3.
(1) If this test gives the maintenance message DMC1 : ATT DSPLY ERR:
- replace the DMC-1 (1WT1) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001).
(a) If the fault continues:
- do a check of the wiring from DMC1 (1WT1) pins AB/9B, 9C to the first terminal block (Ref. ASM 31-61/04).
1 If there is no continuity:
_ - repair the wiring.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-63-81∞∞∞∞∞∞∞∞∞∞Page 243
Feb 01/05R CES
2_ If there is continuity:
- do a check and repair the wiring from DMC1 (1WT1) pins
AB/9D, 9E to the first terminal block (Ref. ASM 31-61/04).
(2) If this test gives no maintenance message:
- replace the PFD-CAPT (2WT1) (Ref. AMM TASK 31-63-22-000-001) and (Ref. AMM TASK 31-63-22-400-001).
(a) If the fault continues:
- do a check of the wiring from CAPT PFD (2WT1) pins AA/35, 36 to the first terminal block (Ref. ASM 31-61/04).
1 If there is no continuity:
_ - repair the wiring.
2 If there is continuity:
_
- do a check and repair the wiring from CAPT PFD (2WT1) pins AA/38, 39 to the first terminal block (Ref. ASM 31-61/04).
B. Do the test given in Para. 3.
Loss of the Altitude Information on the CAPT PFD Detected by the DMC1
1. Possible Causes
_______________
- DMC-1 (1WT1)
- PFD-CAPT (2WT1)
- wiring
2. Job Set-up Information
______________________
A. Referenced Information
-------------------------------------------------------------------------------REFERENCE DESIGNATION -------------------------------------------------------------------------------
AMM 31-60-00-740-002 EIS Input Test
AMM 31-63-22-000-001 Removal of the Display Unit
(2WT1,2WT2,3WT1,3WT2,4WT1,4WT2)
AMM 31-63-22-400-001 Installation of the Display Unit
(2WT1,2WT2,3WT1,3WT2,4WT1,4WT2)
AMM 31-63-34-000-001 Removal of the DMC (1WT1,1WT2,1WT3)
AMM 31-63-34-400-001 Installation of the DMC (1WT1,1WT2,1WT3)
ASM 31-61/04
3. Fault Confirmation
__________________
A. Test
Do the EIS input test (Ref. AMM TASK 31-60-00-740-002).
4. Fault Isolation
_______________
A. If the test gives the maintenance message: DMC1: ALT DSPLY ERR - on the panel 301VU, push the CAPT PFD/ND XFR pushbutton switch (9WT1)
to get the PFD image on the CAPT ND
- do the test given in Para. 3.
(1) If this test gives the maintenance message:
DMC1: ALT DSPLY ERR
- replace the DMC-1 (1WT1) (Ref. AMM TASK 31-63-34-000-001) and (Ref. AMM TASK 31-63-34-400-001).
(a) If the fault continues:
- do a check of the wiring from DMC1 (1WT1) pins AB/9B, 9C to the first terminal block (Ref. ASM 31-61/04).
1 If there is no continuity:
_ - repair the wiring.
「一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一一1 EFF : ALL ∞∞31-63-81∞∞∞∞∞∞∞∞∞∞Page 245
Feb 01/05R CES
2_ If there is continuity:
- do a check and repair the wiring from DMC1 (1WT1) pins
AB/9D, 9E to the first terminal block (Ref. ASM 31-61/04).
(2) If this test gives no maintenance message:
- replace the PFD-CAPT (2WT1) (Ref. AMM TASK 31-63-22-000-001) and (Ref. AMM TASK 31-63-22-400-001).
(a) If the fault continues:
- do a check of the wiring from CAPT PFD (2WT1) pins AA/35, 36 to the first terminal block (Ref. ASM 31-61/04).
1 If there is no continuity:
_ - repair the wiring.