6.  
Following the successful writing to the Configuration Module (no messages) and EGPWC reboot, pressing Control Z (Ctrl Z) restarts the WinVIEWS terminal mode communication.

7.  
There are a couple ways to now confirm the Configuration Module programming with the following being the preferred.  As above, type “CFG” to restart the Configuration sub-mode.  At the CFG > prompt, type “CMR” <ENTER>.  Each Category and its associated ID is read from the Configuration Module and listed on the display. Alternately, when not in the Configuration sub-mode, the command “PS” (Present Status) will display EGPWC and configuration data.

8.  
Configuration Module programming is complete.

 

4.4.1 CONFIGURATION MODULE REPROGRAMMING (MK VI AND MK VIII ONLY)
Reprogramming the EGPWS Configuration Module is accomplished similar to the programming process above. Prior to reprogramming, the desired new configuration should be determined based on the MK VI/MK VIII Interface Control Document (IDG document number 060-4314-125).
For reprogramming the Configuration Module, the following procedure is used:
1.  
Verify EGPWC interface to P2 connector (including Configuration Module) and RS-232 interface to PC.

2.  
Power EGPWC and PC and start WinVIEWS.

3.  
With WinVIEWS active in the Terminal Mode, start the Configuration sub-mode by typing “CFG” at the prompt. At this point, either all the ID’s can be rewritten using the CUW command as before, or individual categories can be changed as follows:

4.  
At the CFG > prompt use the CAT command with the following structure:


.  CAT<space><category #><space><ID#><space><T or F>
.  
<category #> is the ICD Category to change (example 7)

.  
<ID#> is the new ID to change to (example 92)

.  
<T or F> is True or False for rebooting the EGPWC.  Use “T” if only one category is to be changed and the EGPWC will reboot following ENTER.  Use “F” if another individual ID is to be changed by another CAT operation.


Example:
CFG >CAT 7 92 T
5.  
After inputting the desired change information, pressing ENTER will transmit the data to the EGPWC to write to the Configuration Module.  If a reboot is commanded (T), then the EGPWC will reboot at the completion of the write process.  If a reboot is not commanded (F), then the message “Writing to configuration module…Category 7 ID updated successfully.” is given and the CFG > prompt is again displayed.  At this point, the Configuration Module has been changed, but the change will not be effective until the EGPWC is rebooted.  Additional changes can be made with the final change set to command the EGPWC reboot (or cycle EGPWC power to reboot).
 